Gasline Sizing Flashcards

1
Q

What’s the first thing to determine when running a gas line?

A

Type of fuel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

All appliances must be certified for what

A

The type of fuel being used or it can’t be installed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Excessive amount of fittings and directions may cause what

A

Potential problems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What’s the outlet pressure of a gas metre for natural gas?

A

7” to 14” wc

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When running off manifold with gas lines, what needs the safety factors to consider

A

Tagged
No longer then 50 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Where do you find inputs for the appliances?

A

Rating plate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

If MBH value falls between the numbers, what must you do?

A

Go to the higher value

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Before you run a gas line, what must be done

A

Pull a permit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What’s the minimum size face on a test dial gauge

A

3”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Up to 2 psig what is the pressure test requirements for 200 ft or less

A

15 psig for 15 min

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

For 2 psig gas line what is pressure test requirements for 200 feet or more?

A

15 psig for 60 min

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

All wrapped and factory coded piping and tubing. Have to be pressure tested to what

A

Min 100 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

3 inch pressure gauge needs to calibrate in what increments

A

2 psig or 2 percent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Gauge should not exceed the test pressure by at least what

A

15 percent but no higher then 300 percent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

When pressure test is complete what’s the next steps?

A

Purge line to outside no closer than 10 feet to building intake

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

How do you verify a gas line is properly sized

A

Standing pressure test
Operating pressure test

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What’s the maximum allowable drop on gas?

18
Q

Where is standing pressure test taken from?

A

Downstream of service regulator

19
Q

If pressure drops greater than a level limits, what’s the cause?

A

Gas lines too small

20
Q

Every time you do a gas piping installation what must be done

A

Standing and operating pressure test

21
Q

what’s the maximum length of corrugated metal connecter for suspended, appliance, or decorative appliance?

22
Q

A commercial tubing system must be identified at what intervals

23
Q

Can swing joint be installed in a concealed location

24
Q

Propane has a density of what

25
Natural gas has relative density of what
0.6
26
Threaded pipe for natural gas must not be smaller than
1/2 diameter
27
Gas piping or tubing may be made of what material
Steel , copper ,polyethylene
28
What type of copper is approved for underground for gas line?
Type K
29
Polyethylene is non-conductive what needs to be done to locate pipe under ground
14 gauge tracer wire
30
Plastic piping shall not be used for what type of fuel
Liquid propane
31
What’s the minimum rated working pressure for a hose and fittings for appliance connecter
350 psi
32
Maximum length of a hose on permanent installation
10 ft
33
Maximum length of holds on portable appliance, such as barbeque
30 ft
34
Maximum length of flex connecter on vented appliance
2 ft
35
Maximum length of flex connecter on un vented appliance
6 ft
36
Unthreaded of pipe exposed from ceiling, wall and floors are how much
Ceilings and walls, or 1 inch Floor is 2 inch minimum
37
All gas lines are buried, at least how much in depth and how much for a commercial
15” 24” commercial and driveways
38
Alberta public works requires gas lines to be painted what
Orange instead of yellow
39
Isolation valves may be installed horizontally only if they are watt
Located within 2 feet
40
How are gas lines installed on rooftop
Must be supported and painted
41
What’s the maximum spacing for supports for half inch pipe
6 feet
42
What’s the maximum spacing for supports for three-quarter inch?
8 feet