Gas Code Worksheet #1 #2 to edit Flashcards
Which section of theCAN/CSA -B149.1-10 Code does the abbreviations sections follow?
TheDefinitionssection of theCAN/CSA -B149.1-15
Piping or tubing may be supported by any larger pipe in the system
False
Threaded Schedule 40 steel piping may be used for pressures not exceeding ____?
125psi
Underground piping systems shall be joined by means of
Welding and Compression
The volume of gas required for each appliance shall be determined from the appliance rating plate and/or the manufacturers specifications
True
Finish piping and appliance connections shall be checked under test pressure with either a soap solution or a leak detection device
False
An addition to an existing gas line is not subject to Table 6.3 when
Its less than 20 feet in length or its welded
Every hose and hose fitting shall have a minimum pressure rating of ___ psi
350
Natural Rubber may be used as a gasket material
False
A defective section of gas piping or tubing may be repaired by a qualified gasfitter
False
A hose may be used o connect a non vented appliance
Yes
When a piping system is purged outdoors the purge point must no terminate closer than 3 feet from a building or air intake
false
Underground piping or tubing shall not pass below
a foundation wall or under a building
Piping or tubing installed in aa commercial building shall be identified by ____at_____ intervals
Painting the entire gas line yellow
Yellow banding at 20ft intervals
Labelled or marked gas or propane at 20 foot intervals
A corrugated metal connector shall not exceed 2ft in length when connecting to a suspended appliance or a decorative appliance
true
A sleeve must be provided when piping or tubing passes through pavement in order to _____
Permit the free movement of the piping
When a shut off valve controls several systems it shall
Be readily acceptable
Have a handle installed
be protected from damage
be clearly marked
Plastic piping shall only be used underground service
true
Piping or tubing shall never be encased in ducts
false
Nesting of bushing is permitted on low pressure gas piping
False
The maximum range of a test gauge shall exceed the test pressure by at least 15% but not more than 30%
False
A girder beam or joist may be cut for in for installation piping
True
A street elbow or street tee may be used on low pressure gas piping
false
tubing run inside hollow walls within 1.75 “ of the surface shall be protected by 16 gauge plate or sleeves
true
A corrugated metal connector may be used to connect a room heater
true
What is the maximum length of a metal connector for a range is
6 feet
Type L copper tubing may be used underground
true
When an existing piping or tubing system is of insufficient size for additional appliances, the extension shall run a separate line for the new appliance sized for the additional load to with 30 inches of the meter
false
A branch line must be the same diameter as the supply piping when
it supplies an unknown future supply connection
For a portable appliance a hose shall not exceed 75 ft in length
false