G2 Flashcards
A room heater installed in either a sleeping area or public area shall be:
A. Direct vent only
B. Equipped with a regulator
C. Equipped with a fan
D. Equipped with an on/ off switch on the wall
B. Equipped with a regulator
What type of vent must be used when the vent of a wall furnace will be concealed in a partition wall:
A. B Vent
B. L Vent
C. BH vent
D. BW vent
D. BW vent
Single wall vent connectors:
A. may pass through floors, ceilings or roofs provided a metal
thimble is used
B. may pass through floors, ceilings or roofs provided the required
minimum distance from combustible material is maintained
C. may pass through floors, ceilings or roofs provided they are
insulated
D. shall not pass through floors, ceilings or roofs
D. Shall not pass through floors, ceilings or roofs
BW vent shall be used only with an approved:
A. decorative appliance
B. down flow furnace
C. revertible flue boiler
D. recessed wall furnace
D. Recessed wall furnace
What must be done during the installation of a gas log fireplace?
A. Make sure there is a metal mesh screen in front of the fireplace
B. Secure the chimney damper in the open position
C. Install a pressure regulator
D. Install a metal chimney liner
B. Secure the chimney damper in the open position
When can a certified hose be used to connect a construction
heater to temporary piping?
A. Only if a lever handle shut off valve is installed upstream of the
hose
B. Only if the hose is 15 feet long
C. Never
A. Only if a lever handle shut off valve is installed upstream of the
hose
Which of the following is acceptable when a fireplace insert is
installed?
A. A metal chimney linear
B. The existing fireplace flue
C. BW vent
D. A tile lined fireplace flue?
A. A metal chimney linear
An unvented infra-red heater can be installed in ________ application
A. A warehouse
B. A commercial building
C. An industrial building
D. All of the above
D. All of the above
Dirt pockets are required on:
A. Decorative appliances
B. Gas logs
C. Room heaters
D. None of the available choices
D. None of the available choices
What diameter and length of a dirt pocket is required when a drop
line is 3-inch diameter?
A. 3 inch diameter by 3 inches long
B. 1 inch diameter by 3 inches long
C. 3/4 inch diameter by 3 inches long
D. 2 inch diameter by 3 inches long
D. 2 inch diameter by 3 inches long
What type of room heater maybe installed in a bathroom?
A. Natural draft
B. Direct fired
C. Forced draft
D. Direct vent
D. Direct Vent
What safety control protects a steam boiler if the condensate
pump fails to return water to the boiler?
A. High pressure limit control
B. Low pressure limit control
C. Flame safeguard control
D. Low water cut off
D. Low Water Cut-off
The relief valve for a residential low-pressure hot water boiler
system should be?
A. 14.7 psia
B. 15 psia
C. 30 psig
D. 30 psia
C. 30 psig
A backflow prevent used in a boiler system should be located in
the:
A. Over flow line connected to the drain
B. Return line close to the boiler
C. 1/4” line connecting the boiler and cushion tank
D. Make up water line to the system
B. Return line close to the boiler
A 90,000 BTU Category IV furnace shall have a minimum vent termination distance from a Window or door of?
A.1800mm (72in)
B. 900mm (36in)
C. 300mm (12in)
D. 2400mm (96in)
300mm (12 in)
The high limit switch found on category 4 appliance is always wired in series with?
a. The “on” “off” switch
b. Fan blower.
c. Fan motor
d. The gas valve
The Gas Valve
On a furnace with an integrated control board, the blower is controlled by?
a. Timer relay
b. A klaxon(bimetal) switch
c. A combination fan/limit control
d. An ignition module
Timer Relay
If a 24 volts gas valve solenoid is working properly but a humming sound is heard coming from the gas valve, what would be the cause of this?
a. Solenoid coil it broken or burnt out
b. High voltage
c. The common wire is on the wrong terminal
d. Low voltage
Low Voltage
If a thermostat is calling for heat and a volt meter test cross the power source (Transformer) reads 28 volts, another check is done across “RH” and “W” in the thermostat and the reading is “0” volts. This would this suggest?
a. The thermostat need replacing.
b. The transformer need replacing.
c. The transformer voltage too high.
d. The thermostat is good.
The thermostat is good
The best location to install an air conditioning coil on a ‘horizontal or suspended furnace is?
a. Mounted in a frame 3 inches above the air circulating blower.
b. In the supply air plenum
c. In the return air plenum.
d. Air conditioning coils are not recommended for these application
In the supply air plenum
If the warm air supply or the return air supply on a high efficiency furnace is blocked, which component would disable the appliance burner?
a. Solid state board
b. Vent pressure switch
c. Automatic vent damper switch
d. High limit switch
High Limit Switch
A gas FWAF appliance installed in a storage garage shall be at what height from the floor.
a. 8 feet
b. None of the choices
c. 4.5 feet
d. 18 inches
18 Inches
When a high efficiency furnace vent is terminated under a veranda or deck, what requirements must be met?
a. It must be a two pipe system
b. The distance between the top of the vent and the deck underside must be less than 12 inches
c. A minimum of two sides beneath the deck must be open
d. The input must not be over 100,000 BTU
A minimum of two sides beneath the deck must open
The top of a warm air plenum on a furnace should have a minimum clearance to combustible material of?
a.
25 mm
b.
100 mm
c.
75 mm
d.
50 mm
25mm (1”)
A forced warm air furnace is operating at 85% efficiency. If the temperature rise is 78°F and the fan is moving 950 cfm, what is the input?
a.
81 500 Btuh
b.
56,510 Btuh
c.
70 000 Btuh
d.
96 000 Btuh
96,000 btuh
When a furnace is used to heat a residence under construction, what requirements must be met?
a.
The gas connection to the appliance may be done with a flexible hose not exceeding 15 ft.
b.
Must be installed on a finished or poured concrete floor/slab at least 4” thicker; 1” higher than the basement floor, 6” longer and Wider than the base of the furnace.
c.
Shall be fitted with a warm-air plenum and a return-air plenum is not necessary while under construction.
d.
A thermostat is not required while under construction but an “on” “off” Switch may be substituted
Must be installed on a finished or poured concrete floor/slab at least 4” thicker; 1” higher than the basement floor, 6” longer and Wider than the base of the furnace
If a atmospheric category I appliance is equipped with an electrically operated automatic vent damper, when should it operate?
a.
When the appliance surface temperature reaches 140°F
b.
When the furnace main switch is turned on
c.
As soon as gas reaches upstream of the appliance regulator
d.
When the damper is proven to be fully open before ignition of the main burner
When the damper is proven to be fully open before ignition of the main burner
If the domestic water heater using a thermostatic gas valve (unitrol gas valve) what safety device will shut off the supply of gas, if a higher than normal water temp is reached?
a.
E.C.O
b.
Anode
c.
Fire pot
d.
Dip tube
E.C.O.
(Energy Cut Off)
When two water heaters are piped in parallel, it is important to?
a.
Have the largest BTU closest to the door opening
b.
Make sure the vertical outlets are twice the height has the vertical inlet
c.
Ensure that the inlet and the outlet has equal resistance
d.
Ensure that the structure is over 2200 square feet
Ensure that the inlet and the outlet has equal resistance
A temperature and pressure relief valve on a water heater is set relieve at which pressure?
a.
150° F
b.
150 psig
c.
210 psig
d.
210° F
150 psig
What name is given to a water heater that is allowed to be installed in bathroom?
a.
Direct vent water heater
b.
High Efficiency water heater
c.
Power vented water heater
d.
Conventional water heater
Direct Vent water heater