Fourth Year - Block G Specialized Systems[][][][][][][][][][][][][][][][][][][][][][][][][][][][][][][][] Flashcards
What would be the input to an appliance if the meter is a low pressure natural gas meter and it takes 30 seconds for the 2 cubic foot test dial to make one revolution?
240,000 Btuh.
What are some things to take into consideration when deciding where to locate (install) a gas furnace?
Air supply.
Area with proper clearences.
Condensate[][][][][][][][][][][][][][][]
Placed on level surface[][][][][]
Venting[][][][][][][][][][][][][][][][][][][]
Where would you put valves on a gas line when it runs out of one building and into another?
One at each end.
(One as you leave the first building and one as you enter the second building).
What is the manifold pressure for an atmospheric natural gas fired appliance?
3 to 4” w.c.
What is the maximum inlet pressure to the appliance regulator for an atmospheric natural gas fired appliance?
14” w.c.
What is the sequence of components when installing a gas fired unit heater?
A. Drip leg, Manual shut off, Combination gas valve.
B. Manual shut off, Drip leg, Combination gas valve.
C. Combination gas valve, Manual shut off, Drip leg[]
D. Manual shut off, Combination gas valve, Drip leg[]
B. Manual shut off, Drip leg, Combination gas valve.
When replacing an electric boiler on a hot water tank with fossil fuel (gas), what would be some additional considerations?
Air supply.
Clearance from combustables.
Condenstate[][][][][][][][][][][][][][][][]
On an oil furnace, where should the manual shut-off be located?
A. Downstream of the tank but upstream of the appliance filter.
B. Downstream of the filter but upstream of the pump[][][][][][][][]]
C. Downstream of the pump but upstream of the burner fuel valve.
D. Downstream of the burner fuel valve but upstream of the burner.
A. Downstream of the tank but upstream of the appliance filter.
If a gas appliance is added to an existing system and the pressure drop exceeds allowable limits, what must be done.
Connect within 24 inches of the meter or increase the pipe size.
How would you support gas piping that runs on the roof over to a roof top heating unit?
Off the ground.
Roof pipe support.
Treated wood blocks.
When would you need to install a tracer wire with underground gas piping?
On plastic piping.
Which of the following may be used to test natural gas piping?
A. Carbon monoxide.
B. Carbon dioxide[][]]
C. Water[][][][][][][][][][][]
D. Oxygen[][][][][][][][][]
B. Carbon dioxide.
What type of piping may be used for medical gas systems?
Type K or L copper.
(Will say “MED” on pipe).
How is medical gas piping joined?
Brazed with B-CUP 5.
(B = Brazing, Cu = Copper, P = Phosphorous, 5 = Silver content).
How do you purge medical gas systems?
Nitrogen.
(Continuous, oil free dry nitrogen).
What is the colour coding for medical oxygen lines?
Green on a white background.
How are fittings cleaned in medical gas systems?
Tri sodium phosphate.
How do you perfom a cross connection test on a medical gas system?
Test each line seperately with a 5 psig differential between each line.
What system is utilized in order to ensure that the outlets for a medical gas system are hooked up to the correct gas line?
Diameter Index Safety System (DISS) or Pin Indexing.
What should be done in order to prevent cross connections during installation of medical gas systems?
Label as you go.
How should medical gas piping and fittings be stored?
Piping degreased and capped.
Stored in a dry environment[][]]
(Off the floor/Seperate from regular waterpipe).
Stored in sealed bags[][][][][][][][][][][][][][][][][][][][][][]]
Where is the high pressure sensor located on a medical gas system?
Downstream of the pressure regulator.
When working with medical gas piping, where should the discharge piping from an oxygen relief valve discharge?
Outside.
What is the minimum test pressure and duration for a medical gas piping system?
150 psi for 24 hours.