Fire Alarm Flashcards
What is required for all fire alarm systems (new and existing)?
Documentation
What should be delivered upon completion of a fire alarm system?
Owners manual, record drawings, record of completion, site software
Where should all system records be stored?
Documentation cabinet at control unit
What must equipment powered by IDC or SLC be listed with?
Control unit
What are the requirements for a circuit breaker in a fire alarm system?
Requires lock, cabinet lock or locked room door, and be marked FIRE ALARM in red
How many hours of standby power are required for fire alarm systems and supervising stations?
24 hours
What is the minimum alarm power for commercial fire alarms?
5 minutes
What is the minimum alarm power for voice evacuation and MNS?
15 minutes
What is the minimum alarm power for household fire alarms?
4 minutes
How much additional safety margin is required for battery calculations?
0.25
How quickly should secondary power switch?
Within 10 seconds
When should alarm notification, emergency functions, and annunciation occur after activation?
Within 10 seconds
When should supervisory signals indicate?
Within 90 seconds
When should trouble signals indicate?
Within 200 seconds
What are the operational requirements for fire alarm equipment?
85% - 110% voltage, 32 - 120 F, and 85% humidity
Where must smoke detectors be provided?
At control units, NAC extenders, and transmitting equipment
How should each floor be treated in a fire alarm system?
As a separate zone
How should a system serving multiple buildings be zoned?
Each building shall be zoned separately
What is Class A circuitry?
Redundant with a return path, operates with single ground or open
What is Class B circuitry?
Single path, operates up to single open, EOLR on IDC and NAC
What is Class C circuitry?
Multiple paths, no supervision of paths, operation verified by receipt of signal
What is Class D circuitry?
Fail-safe operation
What is Class E circuitry?
No supervision
What is Class X circuitry?
Class A SLC with short, fault isolator per device
What is Class N circuitry?
Network (Ethernet), dual cable/fiber to each Ethernet device or segment
How long should records of tests and operations be kept?
Until next test and one year thereafter
Who is responsible for IT&M of fire alarm systems?
The owner, who may delegate in writing
What type of testing is required for all new fire alarm systems?
100% acceptance testing
What annual tests are required for smoke detectors?
Smoke entry testing and sensitivity testing
How often should smoke detector sensitivity be tested?
Within 1 year, then every other year
If sensitivity remains within range, how long can testing be extended?
Up to 5 years
How often should smoke alarms in dwellings be tested and replaced?
Tested monthly, replaced every 10 years
How should initiating devices be protected?
From damage, with a guard listed with the device
What is required for detectors in concealed locations more than 10 AFF?
Remote indicators (except addressable)
How should partitions extending within 15% of ceiling height be treated?
As separate rooms
Where should detectors be located along the ceiling?
Within 0.7 of listed spacing
How can joist, beam, and slope affect detector placement?
They can affect location and spacing
Where should heat detectors not be located?
Within 4 of sidewall, or between 4-12 from ceiling if wall mount
How should heat detectors be positioned relative to ceiling temperature?
At least 20 F above maximum expected ceiling temperature
How is heat detector spacing determined?
It has a listed spacing that varies