Final Exam Flashcards

1
Q

Two different control approaches

A

Pneumatic

Electronic

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Pneumatic

A

Used compressed air as the operating medium

Almost never used today in modern construction

Stand alone, can’t be networked

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Electric and electronic

A

Typically powered by a 24 VAC power source (usually a transformer mounted on the terminal unit)

Are being replaced by DDC

stand alone, can’t be networked

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

DDC (direct digital control)

A

Most popular and flexible option for most modern buildings

Digital refers to the use of digit computers in these systems

They use analog sensors along with digital computer programs to control HVAC systems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Temp measurements for DDC applications are made by 3 principle methods

A

Thermocouples

Resistance temperature detectors (RTDs)

Thermistors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Thermocouples

A

Consists of two dissimilar metals chosen to produce a measurable voltage at the temp of interest

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

RTDs

A

Use small, responsive sensing sections constructed from metals whose resistance-temp characteristic is well established and reproducible

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

First order resistance equation

R = Ro (1 + kT)

A

R - resistance in ohms
Ro - resistance at reference temp (0 degrees C) in ohms
k - temp coef of resistance
T - RTD temp

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Two common materials for RTDs

A

Platinum

Balco (40% nickel, 60% iron alloy)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Thermistors

A

Semiconductors with the property that resistance is a strong but nonlinear function of temperature

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

VAV CONTROL SYSTEM DIAGRAM

A

See diagram in notes

14 actions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

1

A

When the fan is energized, the control system is activated. Prior to activation, during unoccupied periods, the perimeter zone baseboard heating is under the control of room thermostats.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

2

A

Return and supply fan interlocks are used to prevent pressure imbalances in the supply air ductwork.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

3

A

The mixed-air sensor controls the outdoor air dampers to provide the proper coil air inlet temp. The dampers will be at their minimum position at about 40 degrees Fahrenheit typically.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

4

A

The dampers minimum position controls the minimum outdoor airflow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

5

A

As the upper limit for economizer operation is reached, the OA dampers are returned to their minimum position.

17
Q

6

A

The return air temp is used to control the morning warm up cycle after night setback.

18
Q

7

A

The OA damper is not permitted to open during morning warm up by action of the relay shown

19
Q

8

A

Likewise, the cooling coil valve is de energized (NC) during morning warm up

20
Q

9

A

All VAV box dampers are moved to fully open during morning warm up action of the relay override. This minimizes warm up time because the boxes will almost always be in the closed position. Perimeter zone coils and baseboard units are under the control of the local thermostat.

21
Q

10

A

During operating periods, the PI static pressure controller controls both supply and return fan speeds (or inlet vane positions) to maintain approximately 1.0 inWG of static pressure at the pressure sensor location.

22
Q

11

A

The low temp sensor initiates freeze protection measures

23
Q

12

A

At each zone, room thermostats control VAV boxes (and fans, of present); as the zone temperature rises, the boxes open more.

24
Q

13

A

At each perimeter zone, room thermostats close VAV dampers to their minimum settings and activate zone heat as the zone temp falls.

25
Q

14

A

The controller, using temp information for all zones, modulates OA dampers and the cooling control valve to provide air sufficiently cooled to meet the load of the warmest zone.

26
Q

BACnet

A

Building automation and control network

27
Q

BACnet definition

A

A standard communication protocol developed by the American society of heating, refrigeration and air conditioning engineers (ASHRAE), which has been adopted by the American national standards institute (ANSI) and also by the international standards organization (ISO)

28
Q

CAV CONTROL SYSTEM DIAGRAM

A

9 Actions

29
Q

1

A

When the fan is energized, the control system is activated

30
Q

2

A

The minimum air quality is set (usually only once during commissioning, as described earlier)

31
Q

3

A

The OA temperature sensor supplied a signal to the damper controller

32
Q

4

A

The RA temperature sensor supplied a signal to the damper controller

33
Q

5

A

The damper controller positions the 4 dampers to use outside or return air, depending on which is cooler

34
Q

6

A

The mixed-air low temperature controller controls the OA dampers to keep excessively low temperature air from entering the coils. If a preheat system we’re included, this sensor would control it.

35
Q

7

A

Optionally, the space sensor could reset the coil discharge air PI controller

36
Q

8

A

The discharge air controller controls the

  • heating air damper
  • outdoor air damper
  • exhaust air damper
  • return air damper
  • cooling coil valve after economizer cycle upper limit is reached
37
Q

9

A

The low temperature sensor initiates freeze protection measures, as described previously