an obstructed expansion valve may be indicated by an incompletely cooled evaporator and
frosting at the evaporator inlet
when liquid reached the compressor of a fridge system through the suction line, the condition is called
flooding back (slugging)
the refrigerants referred to as CFCs are
fully halogenated
excessive oil foaming in the crankcase of a fridge compressor can result in
overheated compressor bearings
if you find an extremely large leak while using a halide torch, the flame will
go out
in a fridge system, the heat normally producing the flash gas at the TEV, is obtained from
the portion of liquid refrigerant which does not flash
what device will indicate proper operation of a fridge system dryer
moisture indicator
lube oil should have
a low pour point
a compound gauge is typically installed on the
suction side of a compressor
what is the safest device for testing for ammonia leaks?
litmus paper
increasing head pressure in a fridge system without any corresponding change in the cooling water inlet temp would prob be caused by
air and non-condensibles gases in the condenser
alkylbenzene is miscible and suitable for use with
r-22
if an expansion valve is adjusted for too a superheat value
too much liquid will be passed back to the compressor
during the operation of a large, multi-box system, using a fixed capacity compressor, only 2 of 5 boxes are being cooled. if 2 more boxes started cooling
low side pressure would temp increase
the water regulating valve installed in a system is operated by the
compressor discharge pressure
recovery small appliance after nov 1993
90%
constant superheat is maintained at the evaporator outlet of a coil by a
TEV
ammonia is lighter than air and if a leak should occur it’s concentration will be
of minimum importance during venting
air trapped in a system using a water cooled condenser is usually indicated by
unusually high head pressure when compared with existing temp of liquid refrigerant
foaming of the oil in a refrigerant compressor crankcase is caused by
refrigerant boiling out of solution from the lube oil
overcharging an air-cooled system will cause the
compressor to short cycle
the amount of refrigerant admitted to the evaporator is directly related to
the superheat of the refrigerant in the tail coil
during tests to on a compressor running excessively, it is determined that the refrigerated space temp is nearly normal, the suction pressure is slightly high, and the head pressure is low. you suspect
leak door gaskets
what occurs if the power element of a TEV fails
the valve will move towards the closed position