2 1/2” x 5” adapter attached directly to the pump can deliver ______gpm
1,000 GPM
Def. of Static pressure
When a pumper is connected to a hydrant and Not discharging water. The reading on the intake gauge.
Def of Residual pressure
Once the pump begins to flow water. The reading on the Intake gauge.
Def of Pressure drop
Difference between Static and Residual pressures
First digit method
Static – Residual.
Take first number of Static, multiply by 1,2,3.
etc-
Percent Drop method (4)
10% —-3x the flow
15% —-2x the flow
25% —-1x the flow
>25% water is still available.
Paul Grimwood’s study
Nozzle reaction
1 FF- 60#pounds of force
2 FF- 75#
3 FF -95#
1 kink & 2 kinks reduced flow percentage?
1 kink- reduced flow by 25%
2 kinks reduced flow by 33%
Transfer valve changeover
Less than 50% capacity
Net pressure— All
TV position– Pressure
Transfer valve changeover
More than 50% capacity
Net pressure – LESS than 200 psi
TV position – Volume
Transfer valve changeover
More than 50% capacity and over 200psi
Net pressure –MORE than 200psi
First try to pump in Volume if drafting.
Or in Pressure if working off a hydrant or in Relay.
Only change the transfer valve below _____?
100psi to assure no damage
Kochek Low flow strainer with Jet siphon
800GPM
Min water depth 2”
Jet siphon set PDP at 120 psi
Jet siphon can transfer from one porta tank to another at a rate of 350gpm
Ziamatic QD-600 low flow strainer
2300 GPM
Min water depth 1 1/2”
Can be adjusted and locked through 90 degree arc to assure it sits flat.