EZ-Tump 12 Flashcards
what is EZ-Thump ?
The EZ-Thump is a compact and light weight, battery or AC operated fault location system for low voltage and medium voltage cables.
The resistance between the HV return (operational ground) and safety ground should be less than __Ω (check with ohmmeter).If the resistance is greater than __Ω, what should be done?
5, If the resistance is greater than 5 Ω, an additional ground cable should be connected from the concentric directly to the system ground rod.
name the menu.
the main menu
When in the main menu what is the state of the system ?
int the main menu state, the high voltage source is still switched off and the high voltage output is pulled to ground via a discharge resistor.
Navigation within the available menu items is accomplished using what ?
the rotary knob
how is The currently selected menu item is identified ?
by a red circle.
name the menu.
test modes
name the menu.
pre-location modes
name the menu.
Sectionalizing
what does sectionalizing mode do?
The sectionalizing mode is used to identify and indicate the location of transformers in a loop or radial system and, in the second step, to identify the faulty span of the system.
what is ARM ?
Arc Reflection Method
name the menu.
what is this menu used for?
Locate.
For pre-location of high resistance faults with the EZ-Thump
name the menu.
what does the setting do?
Change visible
range
Changes the displayed range. By doing so, the diagram can be
zoomed in and out.
name the menu.
what does the setting do?
Change NVP
value
the conversion of the distance values (X-axis scaling) can be
directly influenced
name the menu.
what does the setting do?
Set / Move
Cursor
the distance value for any
point on the trace can be obtained