Exam Questions: Low pressure steam and mechanical safety devices Flashcards
Any person involved in the installation, removal, repair, inspection, and servicing of a pressure relief device shall
a) be trained and competent in the duties for which they are responsible
b) hold a class A certificate
a)
Which of the following devices is typically used for steam or vapour service?
a) relief valve
b) a safety valve
c) a safety relief valve
d) a temperature and pressure relief valve
b) a safety valve
Which of the following devices is typically used for liquid service?
a) relief valve
b) safety valve
c) safety relief valve
a) relief valve
What is the usual temperature setting for a temperature and pressure relief valve?
a) 150F ( 66c)
b) 180F (82c)
c) 210F (99c)
d) 212F (100c)
c) 210F
Safety, safety relief, and relief valves shall be of the ___________
a) direct spring loaded type
b) indirect spring loaded type
c) internally weighted type
d) rupture disc type
a) direct spring loaded type
What type of valve may be installed between a boiler and its relief valve?
a) ball valve
b) gate valve
c) globe valve
d) no valve at all
d) no valve at all
A pressure vessel is a closed container that is designed to store, transmit, or convert liquids and vaporous fluids at a pressure greater than ____psi
a) 0.5
b) 15
c) 30
d) q00
b) 15psi
When a vacuum relief valve is used for low pressure steam services a __________ must be installed to prevent live steam from damaging the device
a) air eliminator
b) isolation valve
c) expansion tank
d) pigtail
d) pigatail
What pressures are propane tank safety valves set at?
a) 250 or 312 psi
b) 250 or 375psi
c) 295 or 375psi
d) 312 or 375psi
a) 250 or 312 psi
What pressure is a propane cylinder safety valve set at?
a) 250 psi
b) 312psi
c) 295 psi
d) 375 psi
d) 375psi
What is the LNG secondary relief valve relief pressure set at?
a) same pressure as the MAWP of the tank
b) 1.5 times the MAWP of the tank
c) 2 times the MAWP of the tank
d) 2.5 times the MAWP of the tank
b) 1.5 times the MAWP of the tank