Electronic expansion devices are able to operate near 0F ?
Yes, and they do not have a sensing bulb
If the capillary tube is plugged in the first 6 inches it’s most likely to have what?
Drier desiccant, dirt or copper filings
When pressures are equal in AEV ?
Spring pressure = evaporator pressure or p1=p2
Z charge temperature range is?
0F to -40F
Vapour in the liquid line will dramatically reduce the capacity of TXV?
Yes it’s true
A TXV is said to be balanced when P1=P2+P3. Bulb pressure (opening)= evaporator pressure (SSP)(closing)+ spring force (superheat)(closing)
True
Sizing a capillary tube is done by?
Using inside diameter and length.
An undercharge cap tube system would have symptoms of ?
Low suction pressure
Low discharge pressure
Low amp draw
High superheat
Low side float is found on the low side of the system, opens on a low level of the chiller and is used with flooded evaporators?
True
Captube metering devices are most often used with which compressors?
RSIR
A thermostatic expansion valve type C is good for what evaporator temperature range?
50 to -10F
A TXV with a liquid charge power element has ?
Ability to prevent bulb charge migration
The main function for any metering device is to
Provide a pressure drop
Why would an undercharged high side float possibly starve the evaporator ?
Not enough refrigerant in the system to fill the condenser to the high level which opens the valve or solenoid to allow liquid to enter the chiller. ( evaporator)
Why would in some captube systems the cap tube is brazed to the suction line and covered with armour flex insulation? What is the purpose of this?
To extend the bubble point in a cap tube and also add system superheat.