Evaporator Feed Controls Flashcards

1
Q

Electronic expansion devices are able to operate near 0F ?

A

Yes, and they do not have a sensing bulb

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

If the capillary tube is plugged in the first 6 inches it’s most likely to have what?

A

Drier desiccant, dirt or copper filings

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

When pressures are equal in AEV ?

A

Spring pressure = evaporator pressure or p1=p2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Z charge temperature range is?

A

0F to -40F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Vapour in the liquid line will dramatically reduce the capacity of TXV?

A

Yes it’s true

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

A TXV is said to be balanced when P1=P2+P3. Bulb pressure (opening)= evaporator pressure (SSP)(closing)+ spring force (superheat)(closing)

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Sizing a capillary tube is done by?

A

Using inside diameter and length.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

An undercharge cap tube system would have symptoms of ?

A

Low suction pressure
Low discharge pressure
Low amp draw
High superheat

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Low side float is found on the low side of the system, opens on a low level of the chiller and is used with flooded evaporators?

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Captube metering devices are most often used with which compressors?

A

RSIR

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

A thermostatic expansion valve type C is good for what evaporator temperature range?

A

50 to -10F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

A TXV with a liquid charge power element has ?

A

Ability to prevent bulb charge migration

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The main function for any metering device is to

A

Provide a pressure drop

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Why would an undercharged high side float possibly starve the evaporator ?

A

Not enough refrigerant in the system to fill the condenser to the high level which opens the valve or solenoid to allow liquid to enter the chiller. ( evaporator)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Why would in some captube systems the cap tube is brazed to the suction line and covered with armour flex insulation? What is the purpose of this?

A

To extend the bubble point in a cap tube and also add system superheat.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

A TXV with an X charge is good for what temperature range?

A

-40 to -100F

17
Q

Cap tube systems are typically used with which component ?

A

Accumulator

18
Q

The AEV spring set to maintains a saturated suction pressure and the valve opens and closes on ?

A

Evaporator pressure

19
Q

The first symptom of an overcharged high side float is?

A

Overfilled evaporator and possible flood back to compressor

20
Q

An externally charged TXV must be used when 2 criteria is met?

A

A distributer is used and pressure drop across the evaporator is greater then 2F

21
Q

The AEV would most likely be used in ?

A

Constant load applications , like a slurpy machine

22
Q

What are advantages of a cap tube system ?

A

They are cheep and no moving parts.

23
Q

What are TXV rated by?

A

Tons

24
Q

An externally equalized TXV does it equalize quickly in the off cycle?

A

No

25
Q

If the spring in a TXV lost tension over time, what would you expect your superheat value to be?

A

Less superheat

26
Q

Purpose of a high side float ?

A

Open a valve or energize a solenoid valve when the level of liquid in the condenser reaches its high level.

27
Q

What is the minimum and maximum length of cap tube?

A

6 ft to 18 ft

28
Q

If the bulb of a TXV is not tightly strapped and insulated to the suction line and the box temp is warmer then suction line, the valve will tend to ?

A

Over feed

29
Q

An overcharged low side float system will experience which symptoms?

A

High discharge pressure.