250VDC Battery is sized to ensure how many hours during a LOOP?
3 Hrs
250VDC Battery is sized to ensure how many hours during a SBO?
4 Hrs
If one of the two ground detection lights goes out, which one indicates the ground?
The one that is not lit indicates ground (Could be dimmer than the other as well)
At what voltages on your 250V DC system will you get alarms?
280V DC - High245V DC - Low
Which 250V DC battery has more capacity than the others and why?
U1 CD Battery, because it has additional loads on it (WDS, Drumming Room, MUP, etc)
Where do the BOP battery Chargers get their power from?
BMC/CMC
What is the 250V DC BOP Battery sized for?
2 hrs for LOOP
What load does not strip off the BOP battery?
Emergency Seal Oil pump to prevent H2 from leaking out of generator (explosion hazard)
A 250 VDC station battery is supplying DC bus loads without a battery charger online. If the equipment loaded on the DC bus does NOT change, as the battery is expended the current draw (amps) will?
Rise steadily until the design battery capacity is exhausted
CR Lights are powered by ABT(s)?
ABT 1 and 2
What are ABT’s 1, 2, 3, &; 5 normally powered from for both units?
11A South Lighting Transformer21D North Lighting Transformer
What are ABT’s 1, 2, 3, &; 5 back up power supplies for both units are?
11C Standby Lighting Transformer21C Standby Lighting Transformer
AMSAC Invertor makes 120 VAC to the AMSAC Control Bus for?
Tripping and actuating relays
AMSAC Invertor Makes 24 VDC for?
Control Power for the Relays
What is the TSC-UPS Battery Charger’s normal power supply?
11C
What is the TSC-UPS Charger’s Alt power supply?
12 DGL
What is the TSC-UPS inverter’s Backup power supply?
11A through an isolimiter