ESF Actuations Flashcards
What will cause an SI?
Manual
1/2
Containment Pressure High
3.0 psig (Hi-1) - 2/3
PZR Press Low
1857 psig - 2/4
Steam Pressure Low
735 psig - 2/3 on 1/4 SG
What will cause a Steam Line Isolation?
Manual
Steam Pressure Low
735 psig - 2/3 on 1/4 SG
Steam Pressure Rate
- 100 psig/50 sec*
- 2/3 on 1/4 SG*
Containment Pressure High
3.0 psig (Hi-2) - 2/3
What will casue an AFW actuation?
SG Low Level
20% - 2/4 in 1/4 SG
AMSAC
SI (mode I,III)
full actuation
LOOP (II)
pumps start and recirc, OCIV stay closed
What will cause a Feedwater Isolation?
SI
P-14 - SG High Level
87.5% - 2/4 on 1/4 SG
P-4 with Low Tave
574 F - 2/4 with P-4 true
What will cause a Phase A?
SI
Manual
Containment Pressure High
3.0 psig (Hi-1)
What will cause a Phase B?
Manual
Containment Pressure High
9.5 psig (Hi-3) - 2/4
What will cause a Containment Ventilation Isolation?
SI
High Rad
8012 or 8013
Phase A
Phase B
What will cause an AMSAC actuation?
SG Level Low
- 15% for 25sec with Turbine Power ≥30%*
- 3/4 SGs*