EPA 608 Type III Flashcards

1
Q

30%

A

In 2019, EPA regulations require that leaking industrial process refrigeration with Ozone-depleting refrigeerant be repaired (or retrofitted or retired) when leak rate exceeds 30%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

15 psig

A

The typical design burst pressure for a rupture disk on a low pressure centrifugal ac systems.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Pressure reliefe valves

A

Must NOT be installed in series

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Use of Gloves and sfety goggles

A

A safety precaution that should be adhered to for low pressure systems is the use of gloves and safety goggles when working with liquid refrigerant.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

High Head Pressure

A

Indicates air in a low pressure system.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Compressor Replacement

A

Replacing a compressor always falls under the EPA definition for major maintenance service or repair.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

25 mm of Hg Absolute

A

Technicians must recover refrigerant to a level of 25 mm of Hg absolute before disposing a low pressure appliance.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Extending Appliance Repair Deadlines

A

A certified service tech not being available CANNOT be used as a reason to extend the appliance repair deadlines.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Within 10 days

A

a follow up leak verification test must be conducted within 10 days after a chiller with a charge of 200 pounds of refrigerant has passed the initial verification leak test.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Comfort Cooling

A

The leak repair category defined by the EPA as AC appliances used to provide cooling in order to control heat and/or humidity. Chillers generally belong in the comfort cooling category.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

20%

A

In 2019 the EPA requires that commercial refrigeration systems containing 50 or more pounds of an HCFC be repaired when leak rates reach 20%.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

100 pounds

A

Approximately 100 pounds’ of refrigerant vapor is left in an average 350-ton R-123 chiller at 0psig once all the R123 liquid has been removed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Mothballing

A

In order to mothball an appliance using an ozone-depleting refrigerant, it is NOT required that you remove the appliance and store it in a warehouse at the facility.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

30 days

A

If a chiller containing 150 pounds of HCFC refrigerant is leaking beyond the applicable leak rate threshold, unless granted additional time , you have 30 days to repair the appliance so that if leaks below the threshold and conduct the initial leak verification test.