When using a recovery unit on a system containing 100 lbs. of R-410A it must be evacuated to;
0 inches of Mercury
A comfort cooling system that contains 50 pounds or more of R-410A is leaking. What will be the new maximum allowable annual leak rate starting in 2019?
10%
Leaks must be repaired on industrial process and refrigeration units with a 50-pound charge or greater when the annualized leak rate reaches _____ or more.
30%
What happens to a refrigerant that is heated above the saturation temperature?
It remains in the vapor state.
If a leaking appliance with a regulated refrigerant is not going to be repaired, it must be;
retrofitted or retired within 12 months.
Refrigerant should be recovered from the condenser outlet if the condenser is;
Below the receiver
Refrigerants CFC-12, HCFC-22, and HFC-134a are all classified as Type _______ substances.
A-1
All HVAC/R systems must be protected by a;
Pressure relief valve
EPA regulations state that removal of which component constitutes a “major repair”?
Compressor
Proper recovery techniques begin with the use of appropriate recovery equipment that has been certified by;
EPA approved laboratory
What must the equipment owners/operators include in recovered refrigerant records for equipment with refrigerant charges that range from 5 to 50 pounds?
The quantity of refrigerant (by type) added or recovered from disposed appliances in each calendar month and quantity of refrigerant (by type) sent for reclamation or destruction.
What can be done with a refrigerant trace gas and nitrogen mixture after a system leak is found?
Release to the atmosphere.
When recovering refrigerant from a medium-pressure system with more than 200 lbs. of refrigerant, recover to a level of;
15” Hg
A refrigerant sensor which will sound an alarm and automatically start a ventilation system in occupied equipment rooms falls under ASHRAE Standard;
15
When an appliance containing 50 pounds or more of a regulated refrigerant leaks refrigerant at an annual rate of 125% or more, what must be included on the leak inspections records?
Initial verification, verification tests and records of recovered refrigerant from equipment.