Engine Operating Parameters Flashcards
HT Pres shutdown
3.0 bar
LO Inlet pres shutdown
3.0 bar
HT outlet temp shutdown
97 C
LO inlet temp shutdown
65 C
HT outlet from A or B shutdown
95 C
Main bear temp shutdown
95 C or 2.5 C/sec
TC bearing temp shutdown
120 C
Gen winding high temp shutdown
140 C
Alt bearings high temp shutdown
100 C or 2.5 C/sec
St by engine start by CO2?
Yes
Stby start by HT temp
97 C
Stby start by exhaust gas deviation
70 C
Stby start by woodward minor alarm
Yes
Stby start by alternator load
92%
Stby start by alternator current
90%
Stby start by HT water inlet P
3.2 bar
Stby start by LO inlet P
3.0 bar
Stby start by HT outlet temp
97 C
Stby start by LO inlet temp
65 C
Stby start by nozzle cooling inlet P
2 bar
Stby start by HT outlet by cyl
95 C
Stby start by main bear temp
95 C or 2.5 C/sec
Stby start by TC bearing temp
120 C
Stby start by windings temp
140 C
Stby start by alternator bearing temp
100 C or 2.5 C/sec
Start Blocking LO temp
less than 45 C
Start Blocking HT temp
less than 60 C
Start Blocking Nozzle cooling P
less than 2.5 bar
Start Blocking Nozzle cooling temp
less than 60 C
Start Blocking Fuel pressure
6.0 bar
Start Blocking start air pressure
18 bar
Start Blocking control air pressure
6 bar