At buildings were communication systems are likely to be used, and inter-system bonding termination shall be provided for the communications systems at an accessible location at the service equipment. It shall be an aluminum or copper bus bar not less than 1/4 in thick by 2 in wide and be of sufficient length to accommodate at least________ terminations for communication systems in addition to other connections.
3
The ampacity of a conductor is defined by the NEC to be the maximum current, and amperes, a conductor can carry continuously under the conditions of use without exceeding__________
It’s temperature rating
I disconnect switch and closer install in a class 2, division 2 locations shall be listed as
Dusttight
The interior of enclosures or raceways install underground Shelby considered as a _______ location
Wet
Determine the ampacity (current-carrying capacity) of four size 1/0 awg THE copper current carry conductors install in a common Raceway with an ambient temperature of 86° f.
120 amperes
The NEC states each building or other structure shall have only one disconnecting means unless
The multiple disconnecting means consists of no more then six, and are housed in separate enclosures with a main service disconnecting means in each enclosure
The NEC defines a continuous load to be a load where the maximum current on the circuit is expected to be continued for at LEAST _______ hours or more
Three (3)
Given: You have determined a conductor has a computer ampacity of 74 amperes. What is the MAXIMUM standard ampere rating of the over current protection device the NEC permits to protect this circuit where this is not a motor circuit or part of a multi outlet branch circuit supplying more than one receptacle
80 amperes
A 208-vilt, 3-phase, 50 ho, squirrel-cage, continuous-duty, ac motor has a full-load running current rating of _____.
143 amperes
Which of the following is permitted in the dedicated electrical space above an indoor installed 3-phase, 480y/277-volt panelboard?
Sprinkler protection
Determine the Minimum trade size electrical metallic tubing (EMT) required to enclose eight (8) size 6 AWG copper conductors with THHW insulation, when installed in a 50 foot conduit run.
11/4 in
When exceptions are not applicable, when a feeder supplies a continuous low of 240 amperes, the overcurrent protection device protecting this circuit shall have a rating of at LEAST ______ .
300 Amperes
240 amperes x 125% = 300 amperes
Liquidtight flexible metal conduit (LFMC) shall be securely fastened WITHIN _______ space of each box or other conduit termination.
12 inches or 1’
Where a pull box to be installed will contain conductors of size 4 AWG and larger, and a straight pull of the conductors is to be made, the length of the box shall NOT be less than _______ times the trade diameter of the largest conduit entering the box.
Eight or 8
Conduit or tubing nipples not over 24 inches in length might be filled to a maximum of ______ of their cross- sectional area.
60%
Determine the MAXIMUM Number of size 14 AWG THHN conductors permitted to be installed in a trade size 3/8 in. Flexible metal conduit (FMC) that contains a bare size 14 AWG grounding conductor, when the FMC has external fittings.
4
A device or group of devices that serves to govern, in some predetermined manner, the electric power delivered to the apparatus to which it is connected to, is recognized as a ________ in the NEC.
Controller
What is the MAXIMUM distance permitted between supports of straight runs of threaded trade size 2 in. Ridgid metal conduit (RMC)?
16 feet
A general-use snap switch with an ampere rating of NOT less than _____ shall be permitted as the motor controller for a single-phase 2 hp, 240-volt motor.
24 amperes 12 amperes x 2 = 24 amperes
Which of the following listed types of storage batteries is NOT permitted for use as a source of power for emergency systems?
Automotive. Section 700.12(C)