Electrical Systems Flashcards
Why would we use a Main-Tie-Tie-Main (MTTM) over a Main-Tie-Main (MTM) configuration?
- The extra tie breaker has extra cost but provides more reliability
- In a MTM set-up if the tie breaker fails it will trip all breakers on both buses, for a MTTM a tie breaker failure only clears one bus
- Tie breaker often gets operated and racked-out more than other breakers. In order to isolate, maintain or work on one bus, you need to rack and lock out the Bus B tie, which if you only had a MTM set-up, it means it performs double duty to isolate buses
Why do we have a neutral bar and a ground bar?
Neutral bar collects “grounded” conductors and ground bar collects “grounding” conductors. Grounded conductors carry the unbalanced load of phased conductors and grounding conductors carry fault current. At the main service panel the neutral bar would be bonded to the ground bar via the main bonding jumper. The neutral bar should not be bonded to the ground bar anywhere other than the main service panel.
Why are IR scans useful?
Can use thermal imaging to detect high levels of heat or cold spots which could indicate a problem. Early fault detection can help prevent permanent damage and unplanned downtime.
When would rotary UPS be suited for use?
Rotary UPS would be suited for environments with multiple short inrushes of power, such as where motors are constantly turned on and off.
When do you need an isolating switch?
- When service disconnect is an oil switch or [air, oil, sf6, vacuum circuit breaker]
- Located on supply side of service disconnect
- Not required if service disconnect is rack-out breaker (metal clad switchgear, etc)
What would drive the selection between EMT, RMC, and IMC?
EMT is lightweight “thin-wall” metal conduit and commonly used.
IMC is galvanized steel tubing that can be used wherever RMC is used, but is lighter and easier to work with than RMC
RMC is heavy-duty galvanized steel conduit, and probably used in harsher environments since it is heaver than IMC
What is ZSI?
ZSI is zone selective interlocking.
System in a coordinated distribution system to limit stress on system by reducing the time it takes to clear electrical faults while maintaining coordination. Detects where the fault is and determines whether breaker will open to clear a fault based on trip delay settings or to immediately bypass it.
What is voltage drop?
The longer the length of circuit or cable, the greater the voltage loss. Impact can include problems with motors running more slowly or lights being dimmed. Can be compensated with larger cross-sectional sized cables to offer less resistance/impedance to current flow.
What is VLF tan delta test?
Diagnostic test on cable using AC voltage at low frequency and at lower voltage magnitude than withstand Hi-pot test. Can be used to evaluate overall condition of cables rather than localized defects.
What is VLF AC Hi-Pot testing
Very Low Frequency, AC Hi-pot testing. Uses 0.1 Hz instead of true 60Hz AC testing. Still a withstand test with many of the same problems as DC hi-pot. Designed to grow defects quickly
What is top of rack data center topology?
Two or more switches placed at top of rack at each server cabinet. Servers are cabled to both switches for redundancy. Utilizes cables efficiently, but increased costs and potential for overheating. Also difficult to manage in large deployments.
What is the difference between generator and alternator?
Alternator converts mechanical energy into AC electrical energy. Generator converts mechanical energy into either AC or DC energy. Alternator have rotating magnetic field and a stationary armature. Generators have a fixed magnetic field and rotating armature.
What is the BTU (heat) equivalent to 1 watt?
1 watt = 3.412 BTU/hr
What is short-time delay?
Short-time delay is used in conjunction with short-time pickup to control the time involved in postponing a short-time pickup trip. Mainly used for coordination with downstream breakers and fuses.
What is short time pickup?
Short-time pickup is used for selective tripping. It determines the amount of current the breaker will carry for a short period of time, allowing downstream protective devices to clear short-circuits without tripping the upstream device.
What is voltage sag?
A decrease in nominal voltage or current lasting 0.5 cycles to one minute.
What is overvoltage?
An increase in the nominal voltage for more than 3600 cycles or one minute.
What is long-time delay?
Long-time delay causes the breaker to wait a certain amount of time to allow temporary inrush currents, such as those encountered when starting a motor, to pass without tripping.
What is instantaneous pickup?
Used to trip the breaker with no intentional delay at any current between 2 to 40 times the breakers continuous ampere setting. (Ir)
What is inductance?
It is defined as the property of a coil to resist any changes in electric current flowing through it. Mutual inductance happens when a secondary coil opposes current change in the primary coil.
What is IEEE 80?
Guide for safety in AC Substation grounding
What is harmonics?
Harmonics is the distortion of the ac waveform caused by nonlinear devices in a power system. Harmonics are multiples of the basic waveform, so a second order harmonics is at 120Hz and third order is at 180Hz, assuming a 60Hz power frequency.
What is ground fault pickup?
Controls the amount of ground fault current that will cause the breaker to interrupt the circuit. Can be set from 20% to 70% of max breaker rating, but no trip point setting exceeds 1200A to meet NEC 230.95 (A).
What is continuous amps (Ir)?
Continuous amps (Ir) varies the level of current the circuit breaker will carry without tripping. Ir is a percentage of the circuit breaker’s nominal rating (In), and can be adjusted from 20 to 100 percent of the breakers nominal rating.
What is considered medium voltage?
Medium voltage is a range between 1000V and 35kV
What is considered high voltage?
High voltage is between 35kV and 230kV.
Extra high voltage is anything above 230kV
What are capacitive loads?
Loads where current leads voltage.
Examples can be buried cables, capacitor banks, and capacitors used in various circuits such as motor starters
What is capacitance?
It it the amount of charge that is stored inside a capacitor at a given voltage.
What is an SF6 circuit breaker?
Breaker where sulfur hexafluoride gas is used as the arc quenching medium. Gas is electronegative gas with strong tendency to absorb free electrons. Very effective for high power and high voltage service.
What is an oil circuit breaker?
Breaker oil is used to vaporize arc in the oil when contacts separate.