Electrical Flashcards

1
Q

T/F: The grounded conductor and the grounding conductor are one and the same conductor and perform the same function.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Why are all the​ noncurrent-carrying metal parts bonded together in a wiring​ system?

A) to make the system sturdy
B) to stabilize the voltage
C) to provide a low-resistance path to ground

A

C) to provide a low-resistance path to ground

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What ​NEC® article covers grounding and​ bonding?

A

Article 250

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

In a​ three-phase system, if Phase A conductor contacts Phase B​ conductor, is it a short circuit or a ground fault?

A

Short circuit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

If a circuit breaker ahead of a fault trips at 100 amperes of​ current, what is the maximum value of fault current that may flow through a​ fault?

A) Cannot determine from this info
B) unlimited
C) 100A

A

100A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

If a hot conductor contacts the metal enclosure of a​ panel, is this considered a ground fault or a short​ circuit?

A

ground fault

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What do we have if the neutral conductor contacts a metal receptacle​ box? ground fault or short circuit

A

ground fault

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

T/F
System grounding connects the metal parts of the​ system, like the boxes and motor​ frame, to the electrical​ system’s neutral conductor.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Which one of the following systems does not have to be​ grounded?

A) 24V control circuit
B) 120V household circuit
C) 480V motor power

A

A) 24V control circuit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

To be​ effective, grounding systems must​ _____.

A.
step down the voltage on the primary
B.
protect the system from lightning

C.
monitor the current

A

B. protect the system from lightning

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Which of the following cannot be used as a grounding​ electrode?

A.
Conductive water pipe
B.
Ring made of wire
C.
​10' black iron gas pipe
A

C. 10’ black iron gas pipe

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Where would you find the requirements for sizing a grounding electrode​ conductor?

A.
NEC Article 505
B.
NEC Section 250.50
C.
NEC Table 250.66
A

C. NEC Table 250.66

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Which of the following materials cannot be used as a grounding electrode​ conductor?

A.
Stranded galvanized steel
B.
Stranded aluminum
C.
Solid copper
D.
Stranded​ copper-clad aluminum
A

A. stranded galvanized steel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

T/F: A metal underground tank or metal well casing can be used as a grounding electrode.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Equipment grounding connects to which of the​ following?

A.
Enclosures
B.
​Current-carrying conductors
C.
Neutral conductor
A

Enclosures

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q
What is the EGC designed to​ carry?
Question content area bottom
Part 1
A.
Line voltage
B.
Unbalanced current
C.
Fault current
A

c. fault current

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q
What factor determines the size of the​ EGC?
Question content area bottom
Part 1
A.
Number of duplex outlets in the circuit
B.
Size of the fuse in the circuit
C.
Ambient temperature
D.
Size of the​ "hot" conductor
A

size of the overcurrent protection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Which one of the following methods should not be used to ground a metal residential receptacle​ box?
Question content area bottom
Part 1
A.
A grounding screw secured to the box and designed for this purpose
B.
A grounding clip attached to the box
C.
Wrapping the bare ground around the screw that holds the receptacle

A

C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q
If multiple conduits enter an enclosure and the rules say that these conduits must be​ bonded, must you install a separate bonding jumper from each of them to the grounding terminals at the​ enclosure?
Question content area bottom
Part 1
A.
No
B.
​Yes, if more than three conduits
C.
Yes
A

No

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q
The maximum length of the conductor allowed when running a bonding conductor outside a raceway is​ \_\_\_\_\_.
Question content area bottom
Part 1
A.
5 feet
B.
10 feet
C.
6 feet
D.
not specified in the NECSuperscript ®
A

6’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q
The purpose of an effective grounding path is to conduct any​ \_\_\_\_\_ that might occur in the system.
Question content area bottom
Part 1
A.
fault current
B.
overcurrent
C.
unbalanced current
A

fault current

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q
Which of the following circuits must be​ grounded?
Question content area bottom
Part 1
A.
Secondary circuits in lighting systems
B.
Circuits for electrolytic cells
C.
Circuits for cranes that operate over combustible fibers.
D.
Separately derived systems
A

D. separately derived systems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q
Where must the EGC originate in a separately derived system that originates in a​ transformer?
Question content area bottom
Part 1
A.
At the primary
B.
At the power company
C.
At the secondary
A

A. at the primary

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q
When running power from one building to​ another, must you always run both the EGC and the grounded conductor to the second​ building?
Question content area bottom
Part 1
A.
Only in certain conditions
B.
Never
C.
Yes
A

only in certain conditions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

how long do rebars have to be to be used as ground

A

20’ long, and encased in concrete, and some other conditions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

the metal frame of a building can be used as ground when buried at least how many ft

A

10’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

Rod, pipe, and plate electrodes must have a resistance to ground of less than X ohms

A

25 ohms or less

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
28
Q

A ground ring shall not use less than X gauge copper

A

2AWG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
29
Q

Grounding clamp connection must be made within how many feet from the point where the pipe enters the building

A

within 5’ of the pipe entering the building

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
30
Q

grounding electrodes (ground rods) to be spaced at least X ft apart

A

at least 6’ apart

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
31
Q

what materials can ground rods be made of…

A

stainless steel, iron, steel, copper plated

NOT aluminum

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
32
Q

What table is used to size the grounding electrode conductor?

A

NEC Table 250.66

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
33
Q

What table is used to determine the size of the service-entrance conductor? (determined from ampacity)

A

NEC Table 310.16

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
34
Q

Table 310.16 shows that the service conductor size (copper wire at 75 degrees C) for a 150A service is 1/0 AWG. Which of the three AWG copper electrode conductor sizes below would be used with this service?

No 4
No 6
No 8

A

??

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
35
Q

Which table is: Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment

A

NEC Table 250.122

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
36
Q

Assuming 75 degree copper conductors, a 200A commercial service would require what size service conductor

1/0
2/0
3/0
4/0

A

3/0

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
37
Q
Can a standard ohmmeter be used to effectively measure the resistance of a grounding​ system?
Question content area bottom
Part 1
Yes
No
A

NO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
38
Q
Resistance to earth of a grounding electrode is commonly measured using the​ \_\_\_\_\_ method.
Question content area bottom
Part 1
A.
zero sum
B.
potential difference
C.
​fall-of-potential
D.
​current-zeroing
A

fall of potential

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
39
Q

Which of the following items is not a component of the resistance of a grounding​ system?
Question content area bottom
Part 1
A.
Resistance of the earth around the electrode
B.
Resistance of the conductor connecting the ground electrode
C.
Impedance of any transformers in the system
D.
Resistance between the ground electrode and the soil

A

C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
40
Q
Can a​ three-point resistance test be performed when only one electrode is​ installed?
Question content area bottom
Part 1
A.
​Yes, if the electrode is moved to three separate locations
B.
Yes
C.
No
A

NO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
41
Q
What is the LEAST height above areas accessible to vehicles that electric signs should be when NOT protected from physical​ damage?
Question content area bottom
Part 1
A.
16 feet
B.
18 feet
C.
14 feet
D.
12 feet
A

C. 14’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
42
Q
What is the LEAST amount of free​ conductor, measured from the point in the box where it emerges from its​ raceway, that shall be left at each junction box or outlet box for splices or connection to​ devices?
Question content area bottom
Part 1
A.
6 inches
B.
8 inches
C.
12 inches
D.
4 inches
A

6”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
43
Q
Unless the luminaire is identified as Type IC for insulation​ contact, thermal insulation should not be installed above a recessed luminaire or within how many inches of the recessed​ luminaire's enclosure?
Question content area bottom
Part 1
A.
3 inches
B.
2 inches
C.
1 inches
D.
​1/2 inch
A

3”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
44
Q
When connecting to​ luminaires, trade size​ 3/8 in. flexible metal conduit​ (FMC) is permitted to enclose tap​ conductors, provided the length of the FMC does NOT exceed​ \_\_\_\_\_.
Question content area bottom
Part 1
A.
4 feet
B.
3 feet
C.
8 feet
D.
6 feet
A

D. 6’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
45
Q
Where a lighting track is installed with two​ (2), four​ (4) ft.​ sections, mounted​ end-to-end, how many supports are​ required?
Question content area bottom
Part 1
A.
four
B.
two
C.
five
D.
three
A

D. 3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
46
Q

The EGC for a flexible metal conduit connection to a motor supplied with a 20A circuit is

A. 8 AWG copper
B. 10 AWG copper
C. 12 AWG copper
D. 14 AWG copper

A

check 250.122

c. 12AWG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
47
Q
Touch voltage extends to a distance of approximately  \_\_\_\_\_
A. 1'
B. 2'
C. 3'
D. 4'
48
Q

Ground rod is called

A

Grounding electrode

49
Q

Ground wire is called

A

Grounding electrode conductor

50
Q

In regard to an isolated grounding type​ receptacle, the reason the insulated isolated grounding conductor is purposely NOT bonded to the outlet box is​ _____.

A.
the reduction of electrical noise
B.
preventing the circuit breaker from tripping in the event of a​ ground-fault
C.
ensuring the circuit breaker will trip in the event of a​ ground-fault
D.
the reduction of​ voltage-drop
A

A.

the reduction of electrical noise

51
Q
What is the LEAST depth of contact with the earth needed for a structural support member of a building or structure to be permitted to be used as a grounding electrode regardless of concrete​ encasing?
Question content area bottom
Part 1
A.
6 feet
B.
10 feet
C.
8 feet
D.
20 feet
A

B.

10 feet

52
Q
Where used outside of a​ building, aluminum or​ copper-clad aluminum grounding electrode conductors shall NOT be terminated WITHIN​ \_\_\_\_\_.
Question content area bottom
Part 1
A.
18 inches of the earth
B.
3 feet of the earth
C.
24 inches of the building
D.
6 feet of the building
A

A.
18 inches of the earth

see 250.64(A)(3)

53
Q
When two​ (2) ground rods are used to form the entire grounding electrode system of a​ building, the grounding conductor that bonds the two rods together shall NOT be required to be larger than size​ \_\_\_\_\_ copper, regardless of the size of the​ service-entrance conductors.
Question content area bottom
Part 1
A.
8 AWG
B.
4 AWG
C.
2 AWG
D.
6 AWG
A

D.
6 AWG

see 250.66(A)

54
Q

Bonding Jumpers are covered in NEC Table…..

A

Table 250.102(C)(1)

55
Q

If you are bonding multiple disconnects, with a SEC of 1000 kcmil, the size of the bonding jumper is ___

A

2/0 copper

56
Q

When an equipment bonding jumper is installed outside a raceway, the length is limited to not more than how many feet?

57
Q

The two types of grounding are __

A

system grounding and equipment grounding

58
Q

Systems less than 50V are required to be grounded if the supply voltage to the transformer exceeds ___ to ground

59
Q

Circuits that cannot be grounded include certain circuits for cranes, electrolytic cells, secondary circuits on lighting systems, and isolated power systems in

A

healthcare facilities

60
Q

Grounding methods include an underground water pipe in direct contact with the earth for more than ___

61
Q

The size of the GEC is based on the ___

A

service entrance conductor

62
Q

The size of the EGC is based on the

A

breaker that feeds that circuit

63
Q

The size of the bonding jumper on the supply side is based on the size of the ___ in each raceway

A

service conductors

64
Q

The two main purposes of a neutral in a grounded system are to

A
  1. permit utilization of line-to-neutral voltage

2. create a low impedance return path for fault current to facilitate operation of the overcurrent device

65
Q

Equipment grounding refers to connecting the normally non-current carrying metal parts of equipment to the system grounded conductor and/or ____

A

the grounding electrode conductor

66
Q

which type of system is required to be grounded?

a. systems less than 50V supplied by grounded transformers
b. circuits for cranes that operate over combustible fibers in Class III locations
c. AC systems over 1kV that supply mobile or portable equipment?
d. circuits for electrolytic cells

A

c. ac systems over 1000V

67
Q

A transformer-supplied system operating at less than 50V if the supply voltage to the transformer exceeds ___

A

150V to ground

68
Q

A ground ring of 20’ of No 2 bare copper must be buried no less than ___

A

2.5’ below grade

69
Q

To be effective, a grounding system must limit the voltage on the electrical system and protect it from ___

A

voltage surges

70
Q

Service conductors are sized using Table…

71
Q

The minimum length allowed for driven ground rods under normal conditions is ____

A

8’ minimum

72
Q

The metallic noncurrent-carrying parts of an electrical system are bonded together to ensure ___

A

the proper operation of overcurrent devices in the event of a ground fault, and to prevent differences of potential btw different components

73
Q

The size of the equipment grounding conductor is based on the

74
Q

The main bonding jumper is sized based on the size of the _____.

a) service conductors
b) feeder conductors
c) largest motor load
d) largest overcurrent protective device

A

a) service conductors

75
Q

The key to successfully clearing ground fault currents is _____.

a) maximizing impedance
b) electrical continuity
c) providing multiple electrical paths
d) utilizing threaded couplings

76
Q

According to the NEC ® , the path to ground from circuits, equipment, and metal enclosures
must _____.
a) have sufficiently high impedance to facilitate the operation of protective devices
b) provide a permanent and continuous path sized to safely conduct potential fault current
c) rely on the earth as an effective ground fault current path
d) be capable of safely carrying twice the maximum current of the system

77
Q

The bonding jumper for multiple disconnecting means is located _____.

a) between the feeder panel and the equipment
b) between the equipment and the equipment grounding bus
c) on the supply side of the service disconnect
d) between the equipment and the ground bar

78
Q

A generator system that supplies power where the neutral is not connected to the utility
system, such as for carnivals, is known as a(n) _____.
a) separately derived system
b) autotransformer
c) utility secondary
d) premises-powered system

79
Q

Which of the following is TRUE of the neutral in a grounded system?

a) It prohibits utilization of power at line-to-neutral voltage.
b) It prevents the current-carrying conductor from carrying an unbalanced load.
c) It provides a low-impedance return path for the flow of fault current to the source.
d) It supersedes the operation of overcurrent devices.

80
Q

Which of the following is TRUE when installing grounding at more than one building?
a) The equipment grounding conductor is sized based on the overcurrent device protecting
the first building.
b) The grounded circuit conductor and the equipment grounding conductor must both be
extended to the second building.
c) Only the equipment grounding conductor is extended to the second building.
d) The second building never requires its own grounding electrode.

81
Q

A transformer bonding jumper is routed with the feeder conductors from the transformer to
the equipment grounding bar in the panel and is known as a(n) _____.
a) grounding electrode conductor
b) supply-side bonding jumper
c) equipment grounding conductor
d) equipment bonding jumper

82
Q

A ground tester can be used to measure the value of a grounding electrode’s _____.

a) voltage
b) current
c) resistance
d) capacitance

83
Q

How many ungrounded conductors must be taken from the first structure to where the service
is located in the second structure when running 120V between buildings?
a) 1
b) 2
c) 3
d) 4

84
Q

The fall-of-potential method is used to measure _____.

a) earth resistance
b) step voltage
c) induced currents
d) touch voltage

85
Q
A ground test utilizing an auxiliary current electrode and an auxiliary potential electrode is
known as the \_\_\_\_\_.
a) one-point test
b) three-point test
c) five-point test
d) seven-point test
86
Q
When a new grounding system has been installed, it is advisable to conduct baseline three-
point tests every \_\_\_\_\_.
a) month for the first year
b) season for the first year
c) six months for the first year
d) year
87
Q

Worn motor bearings are most likely to result in a

a. temporary overload
b. sustained overload
c. short circuuit
d. ground fault

A

sustained overload

88
Q

Where in the NEC do you find circuit breaker applications?

A

NEC 240.85

89
Q

Define current rating vs interrupting capacity rating

A

ya do that

90
Q

Every circuit breaker must have its interrupting rating shown on the breaker, unless rated for ___

91
Q

When a common molded-case circuit breaker trips, in what position will the operating handle be?

A

halfway between on and off

92
Q

What is the highest voltage rating for circuit breakers used on DC systems that UL recognizes?

93
Q

Where is the ampere rating located on the circuit breaker?

A

on the handle

94
Q

What is normally the highest short circuit current in residential applications?

95
Q

When does the NEC allow you to use Edison-base fuses?

A

for replacements in existing installations

96
Q

Overloads are often caused by _____.

a) wires crossing
b) motors starting
c) a wire touching a metal frame
d) a bare conductor contacting a metal tool

A

a wire touching a metal frame

97
Q

Which of the following is TRUE regarding overload current?

a) Overload current is confined to normal conductive paths.
b) An overload is the same as a short circuit.
c) An overload is an unintended current path.
d) Protective devices must respond to all overloads.

A

protective devices must respond to all overloads

98
Q

The requirements for overcurrent protection can be found in _____.

a) NEC Article 240
b) NEC Article 344
c) NEC Article 440
d) NEC Article 517

A

NEC article 240

99
Q

Circuit breakers and fuses operate in a similar manner as a boiler’s _____.

a) expansion tank
b) pressure relief valve
c) heat exchanger
d) burner

A

pressure relief valve

100
Q

Which of the following is TRUE with regard to circuit breakers?

a) The interrupting capacity is based on the system load.
b) The interrupting capacity is the same for each voltage level.
c) The interrupting capacity is based on its rated voltage.
d) The interrupting capacity is the same for each frequency.

A

b. the interrupting capacity is the same for each voltage level

101
Q

The frame size of a 20A circuit breaker is _____.

a) 20A
b) 50A
c) 75A
d) 100A

102
Q

The interrupting rating of an FH-type circuit breaker is _____.

a) 5,000A
b) 10,000A
c) 30,000A
d) 65,000A

103
Q
Circuits in which the breaker must be highly sensitive to amperage changes should use a(n)
\_\_\_\_\_.
a) non-automatic circuit breaker
b) ambient-compensating circuit breaker
c) standard magnetic breaker
d) oil circuit breaker
104
Q
A device that trips when a fault current to ground is 6mA or more is designated by UL as
\_\_\_\_\_.
a) Class A
b) Class B
c) Class H
d) Class R
105
Q

The heart is likely to stop when exposed to a current above _____.

a) 5mA
b) 30mA
c) 100mA
d) 200mA

106
Q

Which of the following is TRUE regarding a dual-element fuse?

a) It is a single-use only device.
b) It cannot be used in circuits subject to temporary overloads.
c) It contains a fuse link connected in series with an overload element.
d) It should be oversized to prevent nuisance trips.

A

c. it contains a fuse link connected in series with an overload element

107
Q

Type S fuses are available in sizes up to _____.

a) 30A
b) 60A
c) 100A
d) 225A

108
Q

Which of the following types of drawings helps when sizing fuses for a given application?

a) Single-line schematic
b) Large-scale detail
c) Building elevation drawing
d) Floor plan

A

a single line schematic

109
Q

Cartridge fuses used for branch circuit protection must be marked with the ampere rating,
interrupting rating (if other than 10,000A), and the _____.
a) date manufactured
b) dimensions
c) expiration
d) voltage rating

A

voltage rating

110
Q
The time-current relationship for a number of overcurrent devices connected in series is
known as \_\_\_\_\_.
a) switching
b) looping
c) stringing
d) coordination
A

Coordination

111
Q

Motor nameplates shall include the rated horsepower if ____ HP or more

A

1/8 HP (430.7)

112
Q

The ____ branch circuit is that point from the last fuse or circuit breaker in the circuit out to the motor

113
Q

conductors supplying a single motor shall have an ampacity of ____ % the FLC rating as indicated on the appropriate FLC table

114
Q

The ___ is the device in a motor circuit which turns the motor ON or OFF

A

controller (430.2)

115
Q

A ____ is an assembly of one or more sections with a common power bus and primarily containing motor control units

A

motor control center