Drainage Maximum Fixture Units Flashcards

1
Q

What are the max allowable fixture units for 1-1/4” drainage piping?

Vertical?

Horizontal?

A

V: 1

H: 1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the max allowable fixture units for 1-1/2” drainage piping?

Vertical?

Horizontal?

A

V: 2

H: 1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the max allowable fixture units for 2” drainage piping?

Vertical?

Horizontal?

A

V: 16

H: 8

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the max allowable fixture units for 3” drainage piping?

Vertical?

Horizontal?

A

V: 48

H: 35

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the max allowable fixture units for 4” drainage piping?

Vertical?

Horizontal?

A

V: 256

H: 216

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the max allowable fixture units for 5” drainage piping?

Vertical?

Horizontal?

A

V: 600

H: 428

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the max allowable fixture units for 6” drainage piping?

Vertical?

Horizontal?

A

V: 1380

H: 720

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What are the max allowable fixture units for 8” drainage piping?

Vertical?

Horizontal?

A

V: 3600

H: 2640

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What are the max allowable fixture units for 10” drainage piping?

Vertical?

Horizontal?

A

V: 5600

H: 4680

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What are the max allowable fixture units for 12” drainage piping?

Vertical?

Horizontal?

A

V: 8400

H: 8200

How well did you know this?
1
Not at all
2
3
4
5
Perfectly