Domain 1 Flashcards

0
Q
  1. When troubleshooting a 4-20 mA transmitter, you discover the transmitter is powering off at 100% output. What is the most likely cause?

A. Too much resistance in the loop
B. Too little resistance in the loop
C. Excessive current in the loop
D. Excessive voltage in the loop

A

A. Too much resistance in the loop.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
1
Q
  1. Good manufacturing practice recommends that a test instrument be _________ times more accurate than the unit under test.

A. 2
B. 4
C. 6
D. 8

A

B. 4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  1. The statement: “thermocouple extension wires must have the same thermoelectric properties as the thermocouple that they are used with,” is:

A. True if the extension wires are submerged in the process fluid.
B. True in most installations
C. False. Extension wires must be made from copper or brass.
D. False. The type of extension wire makes no difference.

A

B. True in most installations.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  1. If a current of 9 mA is flowing through a 250 ohm resistor, what would be the voltage drop across the resistor?

A. 12.5 V
B. 22.5 V
C. .225 V
D. 2.25 V

A

D. 2.25 V

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  1. What is the preferred orientation to use when installing a magnetic flowmeter?

A. Vertical, downward flow
B. Horizontal, upward flow
C. Vertical, upward flow
D. Horizontal, downward flow

A

C. Vertical, upward flow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  1. What pressure, in PSI, would be indicated by a properly calibrated absolute pressure gauge that is lying on the workbench at sea level not connected to anything?

A. 0
B. 29
C. 14.7
D. 2.9

A

C. 14.7

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q
  1. A gauge pressure of 195 PSI is roughly what in PSIA?

A. 151
B. 164
C. 178
D. 210

A

D. 210

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q
  1. Which of the following will have the highest pressure difference between the surface and 6 inches below the surface?

A. 12 inch vertical straw filled with water
B. A 10 foot diameter open tank filled with water
C. A 5 foot diameter vertical pipe filled with water
D. None of the above, because the pressure difference in each is the same

A

D. None of the above, because the pressure difference in each is the same

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q
  1. Hydrostatic head is another way of expressing:

A. Gallons
B. Pressure
C. Length
D. Mass

A

B. Pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q
  1. Dividing the density of the process fluid by the density of ______ gives a dimensionless number called specific gravity.

A. Mercury or mercury vapors
B. Oil or natural gas
C. Water or air
D. Any known liquid or gas

A

C. Water or air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q
  1. As the speed (velocity) of a fluid increases through a restriction, the fluid pressure downstream

A. Increases
B. Decreases
C. Remains unchanged
D. First increases then decreases

A

D. Decreases

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q
  1. What Celsius temperature reading is within an oven temperature of 215 to 220 deg. C?

A. 103
B. 110
C. 329
D. 338

A

A. 103

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q
  1. The difference between the indication of the instrument and the actual value of the measured variable is:

A. The controlled variable
B. Called setpoint
C. An error in the measuring instrument
D. Discarded

A

C. An error in the measuring instrument

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q
  1. Hydrostatic head, weight, radioactive properties, density, and sonic detectors are all used in which methods of level measurement?

A. Point
B. Pressure
C. Inferential
D. Direct

A

C. Inferential

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q
  1. Differential pressure transmitters measure level by inference from:

A. Capacitance
B. Conductivity
C. Hydrostatic head
D. Thermal energy

A

C. Hydrostatic head

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q
  1. Thermal elements infer level by measuring:

A. Temperature
B. Capacitance
C. Thermal conductivity
D. Displacement

A

A. Temperature

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q
  1. All of the following types of level instruments can be used to detect the location of liquid services except:

A. Radar
B. Float
C. Hydrostatic head
D. Ultrasonic

A

C. Hydrostatic head

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q
  1. The temperature range of a transmitter is 100 to 200°F. The output signal range is 3 to 15 psig. What would be the expected output signal for an input temperature of 150°F?

A. 6 psig
B. 9 psig
C. 11.25 psig
D. 12 psig

A

B. 9 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q
  1. 75% output on a 4 to 20 mA transmitter is:

A. 12 mA
B. 15 mA
C. 16 mA
D. 20 mA

A

C. 16 mA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q
  1. What is the designation used for a transducer that converts current to voltage?

A. E / I
B. I / P
C. P / I
D. I / E

A

D. I / E

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q
  1. An instrument gives the same indication each time it measures a variable under identical conditions. This defines:

A. Static accuracy
B. Dynamic accuracy
C. Sensitivity
D. Repeatability

A

D. Repeatability

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q
  1. The range of values over which an input signal to a transmitter may be changed upon reversal of direction with no observable change in input is called:

A. Instrument accuracy
B. Reverse precision
C. Zero point
D. Dead band

A

D. Dead band

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q
  1. The steady-state gain of a standard 4-20 mA electronic hydrostatic head level transmitter with a measurement range of 50-250 inches of water is:

A. 0.08 mA / inch of water
B. 0.10 mA/inch of water
C. 16 mA/200 inches of water
D. 20 mA/250 inches of water

A

A. 0.08 mA/inch of water

23
Q
  1. The temperature range of a transmitter is 0 to 200°F. The output signal range is 3 to 15 psig. What would be the expected output signal for input temperature of 150°F?

A. 6 psig
B. 9 psig
C. 11.25 psig
D. 12 psig

A

D. 12 psig

24
Q
  1. Using ANSI / ISA standards, the red lead from thermocouple or extension wire is always the _________ lead.

A. Positive
B. Negative
C. Neutral
D. Ground

A

B. Negative

25
Q
  1. An instrument measurement error is the difference between the actual value of the measured variable and:

A. It’s true value
B. The calibration standard
C. Input and output signals
D. The indication of the instrument

A

D. The indication of the instrument

26
Q
  1. To ensure the accuracy of the pneumatic controller throughout its range, you must precisely adjust all the following except:

A. Supply pressure
B. Input
C. Span
D. Zero

A

A. Supply pressure

27
Q
  1. A device that converts alternating current to direct current is called a:

A. Rectifier
B. Radio station
C. Differential amplifier
D. Comparator

A

A. Rectifier

28
Q
  1. A test instrument that displays the waveform is a(n):

A. Function generator
B. Ammeter
C. Multimeter
D. Oscilloscope

A

D. Oscilloscope

29
Q
  1. What is the measurement in KPa of the pressure transmitter that is reading 20 PSI?

A. 137.9 KPa
B. 13.79 KPa
C. 40.7 KPa
D. 4.07 KPa

A

A. 137.9 KPa

30
Q
  1. Which of the following could be used to calibrate a pressure gauge that is 0 to 800 PSI?

A. Dead-weight tester
B. A Mercury manometer
C. The plant instrument air supply
D. Multimeter

A

A. Dead weight tester

31
Q
  1. 2 psi is equal to ________ inches of water.

A. 1
B. 27.7
C. 14.7
D. 55.4

A

D. 55.4

32
Q
  1. Which of the following is usually adjusted first when calibrating an electronic pressure transmitter?

A. Linearity
B. Span
C. Zero
D. Range

A

C. Zero

33
Q
  1. The calibration plot below shows that the transmitter does need recalibration to correct for:

A. A zero error
B. A span error
C. Both a zero and span error
D. A linearity error

A

A. A zero error

34
Q
  1. The calibration plot below indicates that the pneumatic controller has __________ and must be calibrated.

A. A zero error
B. A span error
C. Both a zero and a span error
D. A linearity error

A

C. Both a zero and a span error

35
Q
  1. __________ is a relative measurement of the time delay between two events, states, or actions.

A. Backlash
B. Dead time
C. Hysteresis
D. Dead band

A

B. Dead time

36
Q
  1. The Reynolds No. determines:

A. The Venturi effect
B. The coriolis acceleration
C. The fluid viscosity
D. If the flow is laminar or turbulent

A

C. The fluid viscosity

37
Q
  1. The flow rate in gpm of water with a specific gravity of 1 provided by a pressure differential of 1.0 psi through a fully opened control valve is a definition of:

A. Cv
B. DP
C. Ov
D. SG

A

A. Cv

38
Q
  1. A plant has a 30 foot high water mounted on top of a 70 foot platform. What is the water level in the tank, measured in feet, if the pressure gauge on the first floor, height 5 feet, reads 40 psi?

A. 22.3
B. 27.3
C. 30
D. 10

A

B. 27.3

39
Q
  1. The 0 to 30 psig gauge is being calibrated. Starting at 0 psi, the technician applies pressure of 15 psi. The gauge reads 14.9 PSI. Then the technician applies 30 PSI. When the pressure is reduced to 15 psi, the reading is 15.2 psi G. What type of error might these readings indicate?

A. Hysterics error
B. Span error
C. Zero shift error
D. Linearity error

A

A. Hysteresis error

40
Q
  1. If the range of a 3 to 15 psi pneumatic transmitter is 50 to 350°C, what is the output signal value, in PSI, at 198°C?

A. 5.7
B. 7.2
C. 8.9
D. 12.6

A

C. 8.9

41
Q
  1. In a test of the accuracy of a pneumatic comparator with a pressure gauge, pressure readings of the test gauge and the gauge being tested are compared at number of test points. Test point readings are made:

A. Only as the pressure is slowly increased
B. Only as the pressure is slowly decreased
C. In no particular sequence
D. As the pressure is increased and the pressure is decreased

A

D. As the pressure is increased and the pressure is decreased

42
Q
  1. A properly calibrated pressure transmitter connected to a 20 foot tall tank with a water level of 15 ft would indicate a pressure of approximately:

A. 19 psig
B. 10 psig
C. 180 inches of water
D. 150 inches of water

A

C. 180 inches of water

43
Q
  1. The span, in inches of water, of a differential pressure transmitter used to measure the full level of a tank that is 5 foot, 6 inches high and contains a process material with a specific gravity of 0.9 should be:

A. 73.3
B. 59.4
C. 66.0
D. 5.6

A

B. 59.4

44
Q
  1. Closing high and low pressure tap block valves, banking the low side to atmosphere, and connecting and applying a known calibration pressure to the high side is done to check:

A. The condition of the block valves
B. Tubing for leaks
C. Zero and span of a DP cell
D. None of the above

A

C. Zero and span of a DP cell

45
Q
  1. When checking the calibration of an instrument, the first information you should record should be:

A. Original span
B. Original zero
C. Calibration data before adjustment
D. Final calibration data

A

C. Calibration data before adjustment

46
Q
  1. The time constant (first order lag) in a transmission system is the time necessary (after dead time) following upset for the response curve to reach ____________ of its final value.

A. 100%
B. 63.2%
C. 50%
D. 37.8%

A

B. 63.2%

47
Q
  1. Load cells and strain gauges measure the amount of material in a tank by measuring:

A. Thermal conductivity
B. Hydrostatic head
C. Ultrasonic frequency
D. Weight

A

D. Weight

48
Q
  1. In the circuit below, what is the total resistance value? (Photo)

A. 9.7 ohms
B. 8.7 ohms
C. 15 ohms
D. 33 ohms

A

A. 9.7 ohms

49
Q
  1. The _________ variable is a part of the process which is adjusted to close the gap between the set point and the value of the controlled variable.

A. Manipulated
B. Measured
C. Controlled
D. Disturbance

A

A. Manipulated

50
Q
  1. The desired value of the process variable is called the _________.

A. Measurement signal
B. Set point
C. Controlled variable
D. Output signal

A

B. Set point

51
Q
  1. An undesired change in a variable which tends to adversely affect the value of a controlled variable, is normally called a(n):

A. Process lag
B. Measurement error
C. Disturbance
D. Error signal

A

C. Disturbance

52
Q
  1. In a home heating system, the room temperature is the:

A. Manipulated variable
B. Set point
C. Controlled variable
D. Disturbance variable

A

C. Controlled variable

53
Q
  1. The integral action which is part of a P&ID algorithm is often called:

A. Rate
B. Reset
C. Gain
D. Insert

A

B. Reset

54
Q
  1. The term “primary element” usually refers to:

A. PID control action
B. Pneumatic control valves
C. Transmitters and transducers
D. Detectors or sensors

A

D. Detectors or sensors

55
Q
  1. Most pneumatic controllers:

A. Produce a 6 to 30 psig output
B. Have some type of flapper nozzle
C. Are PID controllers
D. Can accept a 4 to 20 mA input

A

B. Have some type of flapper nozzle