Dielectric losses and Capacitance test Flashcards

1
Q

Purpose behind Dielectric testing?

A

Measure fundamental AC electrical characteristics of the insulation system for the apparatus under test.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

First thing to setup test for Dielectric testing

A

Short HV bushings and LV bushings together.
Why? Because then entire XFMR are at the same potential, therefore excluding all other systems in the XFMR from the test circuit.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Define “Insulation”

A

A material or combination of suitable non-conducting materials that provides isolation of two parts at different voltages. Properties relating to.. it’s ability to prevent the flow of current, expressed by RESISTIVITY.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Define “Dielectric”

A

A medium in which it is possible to establish and maintain an electric field with little or no supply of energy.

Energy required to establish electric field is recoverable by whole or in part.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How is a dielectric test performed? (3 steps)

A
  1. Apply a signal of AC voltage at power frequency
  2. Measure a response at same frequency as signal. Referenced to applied voltage.
  3. Calculate desired parameters: Measure the fundamental AC electrical characteristics of the insulation system.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How is the measured current separated?

A

Into it’s 2 main components:
1. Reactive component (capactiance in picoFarads and capacitive current in microAmps)
2. Real component (Dielectric Loss via watts loss and Dissipation Factor or % Power Factor)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Resistance is related to what kind of power?

A

Real Power (watts) voltage and current are in-phase. Resistance dissipates energy via heat.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Capacitance is related to what kind of power?

A

Reactive power (VARs).

This is voltage dependent.
Current leads voltage?
Energy Storing (electrostatic field)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Inductance is related to what kind of power?

A

Reactive power (VARs)

Current dependent.
Current lags voltage.
Energy storing (magnetic field)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is Capacitance equal to in a parallel plate capacitor? (give formula)

A

([A]Area of conductors * [e]Dielectric constant)/[d]distance between conductors.

Capacitance permits the storage of an electrical charge, when a potential difference exists between the conductors.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What does the evaluation of the reactive (capacitive) component from our dielectric test tell us?

A

shows physical changes in the insulation system geometry.

We know this because all its variables are physical properties. Area, Dielectric constant, and Distance.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What can cause a physical change to the insulation system?

A

3 things:

  1. XFMR - movement of core/coils
  2. Bushings - shorting of capacitive layers or loss of oil
  3. Arresters - broken elements
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What are suggested capacitance limits as +/- % change from nameplate/benchmark?

A

Less than 5% GOOD
Between 5-10% INVESTIGATE
Greater than 10% BAD - DO NOT PUT BACK IN SERVICE UNTIL ISSUE RESOLVED.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Is it good if capacitance goes down over time instead of up?

A

No, any change of capacitance up or down means there has been a physical change in the insulation system.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What does the evaluation of the Real Component in Dielectric Loss test tell us?

A

the SEVERITY of contamination and/or deterioration of the insulation system.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What are watts a measure of? Give the equation for Watts and explain the correlation between watts loss and the quality of the insulation system.

A

Watts loss (dielectric loss) are measure of the heat losses within the insulation.

Equation for watts loss is:
(W) Watts = (V) voltage x (I) current

The lower the watts loss, the better quality of the insulation system.

17
Q

Dissipation Factor (Power Factor) is the relationship between what?

A

Total Current, Capacitive current, and Resistive current.

18
Q

In a perfect insulation system, what would be the resistive current value? What would the capacitive current therefore be?

A

resistive current would be 0 and the capacitive current would equal the total current. The close the dissipation factor is to 0%, the more efficient the insulation system.

19
Q

Power Factor is equal to what? (formula)

A

Real power divided by Apparent power

20
Q

Why use Power Factor instead of Watts loss?

A

Power Factor is Independent of specimen size. The relationship between resistive current (I-R) and measured current (theta) remains similar.

21
Q

All insulative materials change with what variable?

A

Temperature

22
Q

What is a general limit for Power Factor?

A

Typically 0.5% or less but there are many exceptions.

Compare to previous results, compare to similar/like units, look at trend of this unit.

23
Q

When do you NOT use Power Factor as an evaluation tool?

A

When the measured current is less than 300 microAmps (0.300 mA).

Why don’t we use PF below 0.300 mA?

Because then resistive current is a disproportionally large percentage of the total current and will skew results.

24
Q

What does a “Tip-up test” look for?

A

A tip up test compares two power factors as a function of voltage. One at Line to Ground voltage (L-G) and one at 25% of Line to Ground voltage.

25
Q

What are the six(6) components of a simplified test current?

A
  1. Power Source
  2. Measurement current
  3. High Voltage test cable
  4. Low Voltage test leads
  5. Insulation System under test (XFMR, bushing, etc.)
  6. Test ground
26
Q

Define ‘Grounded Specimen Test’

A

A test that measures current flowing to ground via the measurement circuit.

27
Q

Define ‘Ungrounded Specimen Test’

A

A test that measures current flowing to an ungrounded (floating) measurement circuit

28
Q

Define ‘Kirchhoffs voltage law’

A

Kirchhoffs voltage law states that the directed sum of the potential differences (voltages) around any closed loop is zero.

29
Q

Define ‘Kirchhoffs current law’

A

Kirchhoffs current law states the algebraic sum of currents in a network of conductors meeting at a point is zero.

OR

Kirchhoffs current law states that for any node(junction) in an electrical circuit, the sum of currents flowing into that node is equal to the sum of currents flowing out of that node.

30
Q

How does a negative Power Factor occur?

A

Technically there is no such thing as a negative power factor.

Caused by the presence of a highly resistive leakage path to ground in the circuit (dirty bushing) AND the return mode of that current to the test set (UST)

31
Q

Does a decreased power factor show that insulation has electrically ‘healed’?

A

No. Likely a dirty bushing. Similar to the negative power factor scenario, a change from 0.3 to 0.1 PF means there is a highly resistive leakage path to ground.