DG/PE- Diesel Generators Flashcards
Top dead center (TDC)
When the piston is farthest from the crank shaft as possible
Bottom dead center (BDC)
When the piston is closest to the crank shaft as possible
Swept volume (cylinder displacement)
Volume swept out in the cylinder between BDC and TDC
Equals the product of piston stroke and it’s cross sectional area.
Clearance volume
The amount of space remaining in the cylinder when the piston is at TDC
How crank shaft position is measured
Degrees of rotation before (BTDC) or after top dead center (ATDC)
Engine displacement
The product of the cylinder displacement times the number of cylinders.
what is the purpose of the DG/PE system?
to supply 4160vac to reactor safety related loads
How long does it take a DG to start and attain full-load speed and accept load on a cold start?
10 seconds
What is the rated output of the DG?
5500 KW continuous and 6050 KW for 2 of 24 hours
What signals automatically start the diesel generator?
SIAS
AFAS
LOP
CSAS
Which automatic start signal for DG provides power to the class busses? What do the other three do?
LOP
SIAS and AFAS go to no load, emergency standby mode
CSAS goes to non-emergency(droop) mode unloaded
What is the steady state unloaded voltage of the DG system?
4000-4377 actual
How long does a diesel generator have to be able to support a unit post accident?
7 days
What is the maximum leak rate through the diesel fuel cross connect valves? How long do you have to isolate instrument tubing after leakage initiation?
1.4 GPM
(168 gallons per train)
2 hours to isolate tubing
How does the DG/PE system interface with the DF system?
DF provides on-site storage of fuel oil for at least 7 days of operation
What is DF the system designator for?
diesel fuel oil and transfer system
How does the DG/PE system interface with the PK system?
DC power feed #2, starting circuit, engine panel, low voltage control panels, field flashing power
How does the DG/PE system interface with the NK system?
DG low voltage panel, instrumentation and alarms
How does the DG/PE system interface with the BOP ESFAS Sequencer (SA) system?
.DGSS contact in the BOP ESFAS originates from the module, contact closes on LOP, AFAS, SIAS or CSAS to start diesel in emergency mode.
What is required for the DG when there is a loss of the BOP ESFAS sequencer?
manual sequencing
How does the DG/PE system interface with the SP system?
provides cooling for jacket water, lube oil and intercooler heat exchangers
When the SP system is lost, How long do you have to secure the DG?
15 minutes unloaded
2.6 minutes loaded
How does the DG/PE system interface with the DW system?
DW provides make up water to the DG cooling water system(powered from NH)
What is the maximum leakage rate for jacket water?
1.6 gallon per hour