Corrosion Protection Monitoring Flashcards
Why is a A monitoring regime is necessary
A monitoring regime is necessary to ensure.
The CP system is operating to its design specifications.
There are no in-service affects interfering with it. The amount of current required for protection varies:
From metal to metal.
With the geometry of the structure.
Differences in seawater environment (temp. & pH).
Any other factors that affect the resistance of the
circuit.
Since the amount of current required cannot be accurately predicted, the method of checking is to measure, at various points around a structure.
The Potential & Current Density.
Inspection requirements for CP systems are:
Visual inspection of anodes for wear.
Visual inspection of electrical connections.
Potential measurements to ensure the structure is still the cathode
Current density measurements
Visual & ultrasonic inspection for corrosion
Monitoring Methods include
CP Readings obtained by:
A diver/ROV taking contact readings with a CP meter.
Proximity readings with an ROV mounted probe.
Proximity readings via remotely mounted sensors.
Current Density measurements are obtained by:
Taking readings with an ROV mounted sensor.
Remote electrodes incorporated into the ICCP system.
How is cathode potential measured
The Cathodic Potential is measured by using a reference electrode, incorporated into an instrument that has a readout calibrated in mV (1V = 1000 mV). These are, commonly: High Purity Zinc (Zn). Silver/Silver-Chloride (Ag/AgCl). Copper/Copper-Sulphate (CSE) (more favoured for concrete structures).
Explain High Purity Zinc Electrode (ZRE)
It may be installed as part of an Impressed Current System 99.9% pure is common Site for mounting the electrode is selected because:
It is a representative site
Area of marginal protection
Area of high stress The electrode is connected to a voltmeter on the surface
What is the most common reference cell
Silver/Silver-Chloride (Ag/AgCl).
Most common reference electrode used offshore.
Used for both contact & proximity applications.
Referred to as half-cells, as they form a ‘cell’ when the meter is connected to the cathode.
Probe tip is placed on the cathode (metal to metal) & the meter gives the readout in mV of the electrical potential between it & the half-cell.
Explain a Monitored Anode
Similar to reference electrodes, but can be used to monitor the efficiency of any CP system.
A sacrificial anode, isolated
electrically from the structure.
Connected to an ammeter in
the control room. Current density may also be measured using a specialised ROV mounted probe.
Why is Calibration Checking necessary
It’s necessary to confirm calibration of CP meters.
To ensure that the readings are accurate & comparable with previous readings.
A standard method has been adopted in the offshore industry for this purpose.
What is the first part of calibrating
The first part of the procedure, is to prove that the reference electrodes, either:
K-series or Calomel Cells
are chemically saturated & sufficiently stable enough to be used as reference cells.
What equipment is needed for calibration
Necessary Equipment.
3 K-series or Calomel Electrodes c/w electrical connectors.
High Impedance (10 MΩ) voltmeter.
Zinc block (99.9% pure) c/w clamp & electric connector.
Plastic bucket of fresh seawater.
Log sheets.
How do you prove the k cell
Visually inspect the electrodes to ensure they are undamaged & full of solution (Potassium Chloride).
Label them 1, 2 & 3.
Soak in the bucket for 24 hrs.
Connect 1 to the neg. terminal of the
voltmeter & connect 2 to the pos. & record the
reading.
Repeat the test with each permutation.
If all readings are within this range, any cell may be used.
If all readings are out of this range, either replace all cells.
Or flush out the phials with pure distilled water, refill with Potassium Chloride & re-test.
After the procedure, rinse the cells in freshwater.
What is the reading is good for k cell
+/- 2mv
What procedure happens next
Once satisfied that the electrical components are functioning correctly:
Fully charge the CP meter batteries and soak in fresh seawater (not drawn
from the fire main).
Remove the contact probe tip and white Delrin probe cone from the meter.
Screw the K-series reference electrode onto the Bathycorrometer in place of
the Delrin probe and probe cone tip.
Immerse the meter in the bucket at least far enough to submerge the semi-
permeable membrane. Gently shake the unit to remove any air bubbles
lodged in the holes. (The meter display may be left out of the water to
assist taking readings).
Allow time for the meter to stabilise (approximately 10 minutes).
The voltage potential between the reference electrode and the meter’s own
Ag/AgCl cell is read off the meter display directly.
Record the reading on the log.
Acceptable readings are +42mV +/-5mV. It should be noted that values will vary dependent upon salinity and temperature of the seawater, see Figure 10.7
The calibration of other types of contact CP meters is by comparison.
Procedure for use of cp meter
Ensure meter is fully charged (approx. 15 hrs).
Maintain a battery-charging log.
Ensure the probe tip is sharp.
Soak for 30 minutes before use.
Confirm the calibration of the system.
Record the results on the log sheet.
Record meter serial number on the log sheet.
During use what are the procedures
Take a reference reading on zinc prior to the survey.
Ensure correct metal-to-metal contact.
Proximity probe must have a electrical connection to the structure connected to the positive terminal of the voltmeter & the standoff is a max. 100mm.
Ensure that each reading is recorded in the log.
On completion, take a reference reading on zinc.