Controls & Instrumentation Flashcards
In nearly all LP steam heating systems the feedwater:
a) Is usually condensate
b) Requires daily close scrutiny of chemical values
c) Is a high make-up percentage
d) Must be deaerated
e) Requires preheating in an economizer
a) Is usually condensate
When a boiler equipped with a combination feedwater control and low water cut-off device shuts down due to a low water condition:
a) The feedwater flow will also stop
b) The level must be restored to above the cut-off line before the unit can be restarted
c) It can be restarted by simply resetting
d) A manual reset switch must be used
e) A pre-purged will not be necessary
b) The level must be restored to above the cut-off line before the unit can be restarted
An electric feeder valve will:
a) Eliminate the need for low-water fuel cutoff
b) Prevent a low-water trip
c) Open before the low-water cutoff line is reached
d) Require manual action to open
e) Open after the nit trips on low swater
c) Open before the low-water cutoff line is reached
The result of a condensate receiver that is too small could be
a) High boiler water level(s)
b) Loss of condensate to the sewer
c) Loss of make-up water
d) Unacceptable high steam pressures
e) Low make-up water flow rates
b) Loss of condensate to the sewer
The feedwater supply to most heating boiler is controlled by a ____________ switch
a) Solenoid
b) Float
c) Differential pressure
d) Drum level
e) Pressure
b) Float
As a general rule the size of the condensate receiver should be large enough to hold a volume of condensate equal to the water evaporated by the boiler in a/an ______ hour period
a) Two
b) One and one half
c) One
d) three quarters
e) One half
e) One half
Prior to a boiler safety valve popping during routine boiler operation:
a) A try lever test should be performed
b) The pressure gage should be checked
c) The high limit switch should be open
d) The feedwater pump should stop
e) The high level alarm should sound
c) The high limit switch should be open
A test lead or “jumper wire” is required when testing:
a) High steam pressure or water temperature limiting controls
b) A high gas pressure fuel cutoff switch
c) A safety valve with the test lever
d) the low water fuel cut-off switch
e) A low gas pressure fuel cut-off
a) High steam pressure or water temperature limiting controls
Modulating burner controls operate by regulating:
a) Steam flow and fuel flow
b) Fuel temperature and air flow
c) Fuel flow, air flow, and feedwater pressure
d) Fuel flow and air flow
e) Fuel flow and atomizing steam flow
d) Fuel flow and air flow
A low fire switch:
a) Is a type manual override
b) Takes no part in the start-up of an automatic boiler
c) Acts as an interlock to ensure minimum damper setting
d) Utilizes a thermal element for its operation
e) Is a normally closed switch
c) Acts as an interlock to ensure minimum damper setting
High limit temperature controls:
a) Increase air flow to the boiler if temperature limits are exceeded
b) Open a 3-way mixing valve to add cold water to the hot water to reduce the water temperature
c) Shut off the fuel if the water temperature is too high
d) Are required under section II of the ASME codes
e) are required on steam boilers
c) Shut off the fuel if the water temperature is too high
A thermal element is:
a) Used to measure pressure
b) Capable of sensing temperature and converting it to a pressure signal
c) A type of open system
d) Used to measure heat content
e) Commonly termed as “Aquastat”
b) Capable of sensing temperature and converting it to a pressure signal
Combustion air safety switches are commonly found:
a) On a natural draft boiler
b) On hot water boilers only
c) On boilers utilizing a forced draft fan
d) As non-interlocking devices and take no part in a start up
e) On gas fired boilers only
c) On boilers utilizing a forced draft fan
During the start-up, a boiler equipped with an automatic control system and a flame, scanning device, the main fuel supply valve:
a) Must be opened before ignition can take place
b) Can be opened before the flame scanner sees a flame
c) Can be opened any time during the start up sequence
d) Should be opened as soon as the pilot valve opens
e) Must be closed before ignition
e) Must be closed before ignition
A flame scanner:
1) Requires a photoelectrical cell
2) Responds to temperature changes
3) Requires a clear line of sight to the flame
4) Produces a steady voltage signal
2) Responds to temperature changes
3) Requires a clear line of sight to the flame
Flame safeguard devices:
a) Should be tested following the manufacturers instructions
b) Should be kept as far as away form the fire as possible
c) Should not be cleaned except by a qualified serviceman
d) Should be kept cool enough to be touched by hand
e) Are all unaffected by heat
a) Should be tested following the manufacturers instructions
Which of the following is a flame, sensing device?
a) Thermopile
b) Heat sensing control
c) Stack relay
d) Cut-off valve
e) Scanner
e) Scanner
A thermocouple:
a) Consist of two similar wires
b) Produces a electrical signal
c) Senses infrared light from the flame
d) Senses changes in fuel line pressure
e) Senses changes in air pressure
b) Produces a electrical signal
The function of a flame failure device is to:
a) Shut off the fuel supply when the pressure gets too high
b) Shut off the fuel when the burner flame goes out
c) Shut off the fuel when the fuel temperature is high
d) Shut off the feedwater supply to the boiler
e) De-energize the fan and feedwater systems
b) Shut off the fuel when the burner flame goes out
A pneumatic control system:
a) Uses a sensing device to change pressures in the control line
b) Requires an internal air supply
c) Always uses pressure actuated final controlled devices
d) Is not used to control air flow for ventilation
a) Uses a sensing device to change pressures in the control line
A pneumatic control system consist of which of the following essential parts:
1) an air compressor with storage tnak, filter, and reducing valve
2) Air piping and tubing forming the air distribution system
3) Controllers such as rheostats
4) Controlled devices such as convectors valves, zone valves, and damper operators
1) an air compressor with storage tnak, filter, and reducing valve
2) Air piping and tubing forming the air distribution system
4) Controlled devices such as convectors valves, zone valves, and damper operators
Dual temperature thermostats are set at two different temperatures and the transfer from one to the other is made by, changing the supply air pressure from:
a) 3 to 15 KPa
b) to 25 KPa
c) 20 to 90 KPa
d) to 100 KPa
e) 100 to 125 KPa
e) 100 to 125 KPa
In the pneumatic control nozzle and vane system the:
a) Vane approaches the nozzle increasing air pressure
b) Vane approaches the nozzle decreasing air pressure
c) Nozzle pressure increases moving the vane further away
d) Nozzle pressure decreases allowing the vane to move closer
e) Vane and nozzle move to maintain equilibrium
a) Vane approaches the nozzle increasing air pressure
In a non-bleed type controller the device that senses a change in room temperature is the:
a) Sensing valve
b) Bellows
c) Set point gauge
d) Temperature switch
e) Feedback switch
b) Bellows
A non- bleed controller bleeds control air:
a) When the supply pressure is decreased
b) When the supply pressure is increased
c) Non-bleed controllers do not bleed air
d) When the control air pressure is increased
e) When the control air pressure is decreased
e) When the control air pressure is decreased
Thermostats may be classified a cording to there:
a) Application
b) Type of temperature sensing element
c) Type of control action provided
d) temperature range
e) All of the above
e) All of the above
Controls motors are divided into two classifications:
a) Large and small
b) AC and DC
c) Valve operators and dampers operators
d) High voltage and low voltage
e) Pump and fan controllers
c) Valve operators and dampers operators
Using electricity for control purposes has the following advantages:
a) It is readily available
b) The wiring is usually simple and easy to install
c) Signals from sensing elements can produce one output
d) Controllers/actuators do not require an air supply
a) It is readily available
b) The wiring is usually simple and easy to install
d) Controllers/actuators do not require an air supply
In a basic control system an example of a controlled device is:
a) A fuel valve
b) A damper
c) A diverter valve
d) An electric switch
e) all of the above
e) all of the above
ON-OFF thermostats are equipped with:
a) An open contact switch
b) A high temperature switch
c) A low temperature switch
d) A high voltage switch
e) A low voltage switch
a) An open contact switch