Control Interlocks Flashcards
C-1
IR Hi Flux Rod Stop
IR NIS > 20%
1/2
Stops ALL Rod OUT Motion (Blocked by (P-10))
C-2
PR Hi Flux Rod Stop
PR NIS > 103%
1/4
Stops ALL Rod OUT Motion
C-3
OTΔT Rod Stop
114% (± Penalties)
Inputs: PR NIS (∆I > +8%) / Tave / Pzr Pressure < 1.5% of Setpoint
2/4
Stops ALL Rod OUT Motion
C-4
OPΔT Rod Stop
∆T < 100% ∆T ( 1.08 -0.02/◦F(T rate) - 0.002 (T-592 ◦F) - ∆I
∆I set to zero
STPT 108%
< 1.5% of Setpoint
2/4
Stops ALL Rod OUT Motion
C-5
Low Turbine Impulse Pressure Rod Stop
Impulse Pressure (PT-505) / Inlet Press* < 15%
1/1
*UNIT 1 ONLY Uses average of
PT-505/506 OR average of
PT-7483/7484 as selected
C-7
Steam Dump Load Rejection
Impulse Pressure (PT-506) / Inlet Press*
> 10% Step Load Loss
OR
5%/min Load Loss
1/1
Arms Steam Dumps in Load Reject Mode with (C-9) Tave Mode with Variable Setpoint for Load
*UNIT 1 ONLY uses average of PT-7483/7484
C-8
Turbine Trip
EH Pressure < 1245.8 psig
(2/3)
OR
TV Valves Closed
(2/4)
Rx Trip (P-9 is True)
Main Generator Trip
Arm Steam Dumps in Trip Mode
Tave Mode with Setpoint of No Load: 567 F
C-9
Condenser Available for Steam Dumps
Condenser Vacuum > 22” Hg
(2/3)
AND
> 1 CW Brkr Closed
Allows Steam Dump Operations
C-11
Top Rod Stop
CR Bank D
> 248 Steps
Stops AUTO Rod OUT Motion
C-17
Stop Turbine Loading
Lo-Tave < Tref (>17*F)
OR
Tave <563*F
Blocks Raising Turbine Load
C-20
AMSAC Armed
Impulse Pressure >30%
2/2
Arms AMSAC