Contactor And Motor Starters Flashcards
What would be the next step if 240v is measured at L1&L2 of the contractor, but 0volts is measured at the T1&T2 terminal?
Measure for voltage at the contractor coil
What is the maximum allowable voltage drop across the contacts of a contractor,before it needs to be replaced or repaired?
3%
Discolored contacts(burnt) on a contractor indicates the contacts are faulty
False, test across contacts for voltage drop.
Chattering contacts in a contractor can be caused by which of the following?
Faulty contacts, low coil voltage, loose electrical connection (All of the above)
Infinite resistance (OL) measured across the coil connections on the contractor indicates
The coil is open and the contractor or coil needs to be repaired