Contactor And Motor Starters Flashcards

1
Q

What would be the next step if 240v is measured at L1&L2 of the contractor, but 0volts is measured at the T1&T2 terminal?

A

Measure for voltage at the contractor coil

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the maximum allowable voltage drop across the contacts of a contractor,before it needs to be replaced or repaired?

A

3%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Discolored contacts(burnt) on a contractor indicates the contacts are faulty

A

False, test across contacts for voltage drop.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Chattering contacts in a contractor can be caused by which of the following?

A

Faulty contacts, low coil voltage, loose electrical connection (All of the above)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Infinite resistance (OL) measured across the coil connections on the contractor indicates

A

The coil is open and the contractor or coil needs to be repaired

How well did you know this?
1
Not at all
2
3
4
5
Perfectly