1
Q

What are the CBP auto starts?

A
  • Low pressure at 325#
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the flow capacity of the LP #1 heaters?

A
  • Each string supplies 50% flow (We have 3)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the flow capacity of the LP #2-4 heaters?

A
  • Each string supplies 80% flow (we have 2 strings) with a bypass that can provide 20% flow via CRV-224
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What does CRV-55 do for you?

A
  • Allows makeup from the CST to the Condenser Hotwells (Sensed on A and C hotwell lvl)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What does CRV-155 do for you?

A
  • Allowd for excess condensate from hotwells to go back to the CST (Sensed on A and C hotwell lvl)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What does CRV-224 (2,3,4 Heater bypass valve) do?

A
  • Allows having a heater string out and provides 20% flow
  • Auto modulates open when MFP suction < 240#
  • Trips open at 210# MFP Suction #
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How do you reset CRV-224 (2,3,4 Heater bypass valve)?

A
  • To reset, MFP Suction pressure > 260# and run controller to open
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What do CRV-201-203 (Condensate Booster Pump Recirc Valves) do?

A
  • Maintain 4000 gpm on running pumps

- ** Flow switch is on the common discharge header**

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where is the flow switch located for the Condensate Booster Pump Recirc Valves?

A
  • ** Flow switch is on the common discharge header**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What do CMO-101(102) (SJAE bypass valves) allow?

A
  • Manually position to achieve desired DP across SJAEs

- Prevents exceeding design flow of SJAEs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What does CMO-61 (SJAE and HWP recirc line valve) do for you?

A
  • Provides continuous flow path from steam jet air ejector header to the main condensers to maintain minimum flow through the hotwell pumps and steam jet air ejector condensers
  • 2400gpm min per pump
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What suction pressure do the CRV-224 valves help to maintain?

A
  • 210#-240#
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What actuates hood spray in Unit 1 (CRV-102) and Unit 2(CMO-40)?

A
  • Generator Load < 7.5%
  • Turbine Speed > 900 rpm
  • Manual
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

When does U-1 Hood Spray Terminate?

A
  • All exhaust hood temperatures are < 160 °F,
  • Generator load is > 12.5%
  • Turbine speed is < 900 rpm
  • 1-CRV-102 Fails CLOSED on loss of air or power.
  • Manual
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

When does U-2 Hood Spray Terminate?

A
  • CMO-40 will close if either SRV 26 and/or 27 are NOT full open
  • 2-LPS-17 is < 30 psia.
  • Generator Load > 12.5%
  • Turbine Speed < 900 rpm
  • CMO-40 fails AS IS on loss of power.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When does hood spray in Unit 1 (CRV-102) and Unit 2(CMO-40) auto close?

A
  • Generator Load > 12.5%

- Turbine speed < 900 rpm