Compressor Problems And Failures Flashcards

1
Q

What happens if moisture gets into the system?

A

Causes acid to form in the oil. The acid attacks the insulation on the motor windings and can cause a short circuit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the causes of a compressor having low oil?

A
  • low refrigerant charge or low load low mass flow of refrigerant will not return oil
  • inadequate evaporator defrosting or froze evap
  • short cycling of the compressor pumps oil out of the crankcase, but does not run long enough to pull it back
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is flooding?

A
  • a continuous stream of liquid refrigerant returning to the compressor
  • refrigerant washes away the oil from the cylinder walls during the suction stroke without lube wearing out the cylinder walls causing blow by into crankcase
  • check for proper superheat or 20 degrees farenheit system superheat at the compressor
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is slugging?

A
  • on suction cooled compressors, the effect of slugging is a more rapid process of displacing oil with refrigerant
  • causes immediate compressor failure
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What kind of damage does Slugging cause on a compressor?

A
  • Damaged reed valves
  • damaged head gasket
  • damaged connecting rods and crankshaft
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the causes of Slugging? And what are the cures?

A
  • Refrigerant oil lying in the suction line
  • Severe overcharge in a critically charged system using a fixed metering device
  • the TEV is stuck open
  • Check for proper superheat or use a pump down system to resolve issue
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What temperatures should a recip compressor never exceed?

A

225 - 300 degrees farenheit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

At what temps does lube oil start to lose its ability to lubricate?

A

300 - 320 degrees farenheit

350 for break down

How well did you know this?
1
Not at all
2
3
4
5
Perfectly