Components and Operation of the Way-Wolff Water/Steam System Flashcards
The burner unit in most CG applications consist of four separate systems. These subsystems are:
- Water system/Steam system
- Electrical system (includes ignition & control components)
- Air system
- Fuel system
As steam is condensed in the steam system, it is returned as water to the _________ where it is stored.
Condensate Tank
A condensate or feed pump is used to pump water from the condensate tank to the _____.
Boiler
A check valve and soleniod valve are installed between the pump discharge and the boiler water inlet connection to prevent _________.
back flow of water through the pump
A stop valve is provided to isolate the boiler from the pump for?
Maintenance
A float switch is installed omn the tank to prevent the pump motor and soleniod valve from becoming energized in the event the condensate tank water level is?
Low
Two, two inch fittings are provided at the bottom of the _____.
Water Drum
Washout/Inspection openings: One of these fittings is located at the lowest point on the ______.
Boiler Shell
Washout/Inspection openings: It is used to control sludge in the boiler shell.
The fitting located at the lowest point on the boiler shell.
During normal operation of the Way-Wolff, the water level in the sight glass should be approximately ____.
Half Full
How many tri-cocks are installed on the boiler shell?
Two
They are primarily used as an alternative method of checking the boiler water level in the event the sight glass is inoperative.
Two tri-cocks installed in the boiler shell
During normal operation, opening the top tri-cock valve should discharge_____.
Steam
During normal operation, opening the bottom tri-cock valve should discharge_____.
Water
A _______ is connected to the 4-inch NPT opening near the boiler top. It is used to discharge steam to the ship’s steam system.
Steam Discharge Valve
A steam pressure relief valve is connected to the upper boiler shell to relieve excess pressure in the event of over pressurization. It is set to relieve at ___ PSI and vents to the atmosphere.
30 PSI
A steam pressure gauge is connected to the upper boiler shell and it is used to indicate?
Operating Pressure
How many blowdown valves are located on the boiler?
Three
When are blowdowns done?
Daily or when the total dissolved solids is above 1000 PPM
This is the primary device to control the start and stop sequence of the burner.
The Operative Pressure Control Switch
A safety device designed to shut down the burner in the event that the operative pressure control does not secure the boiler at the normally prescribed cutout point of 26 PSI.
The High Limit Pressure Control Switch
If the High Limit Pressure Control Switch cut out, it must be manually reset. What PSI is it adjusted to cut out at?
28 PSI
The high limit pressure control switch consist of 2 adjustments, one to set the cut-out point & one to adjust the differential. It is set to cut out at ___ PSI with an 8 PSI differential.
26 PSI
What are the 3 general warning/indicator lights on the control panel?
- Flame-out light
- Low water light
- Power-on light
A red _______is provided on the control panel which will illuminate anytime the FSC goes through a flame-out condition.
Flame-out light
A blue _______ is provided on the control panel which will illuminate anytime the low water cutoff probes indicate a low water condition.
Low water light
A white ______ is illuminated anytime the main disconnect switch is closed and 110 volts power is available to the control panel. However is does not indicate power on the secondary side of the five ampere fuses which provide power to the FSC.
Power-on light
The ______ is used to control boiler operation based on a safe water level in the boiler.
Low Water Relay
The ______ is located in the control panel and serves to energize or de-energize the burner motor.
Motor Relay
The _______ is located on the top of the boiler. The motor drives a squirrel cage type blower which provides combustion air to the combustion chamber. The fuel pump which pumps fuel to the nozzles is also attached to the driveshaft.
Burner Motor
Two ________ are provided in the control panel. Their purpose is to energize an audible alarm in the event of low water or flame failure. One relay is for flame failure & the other is for low water failure.
Alarm Interlock Relays
An _______ is provided to silence the audible alarm. However it does not de-energize the alarm indicating lights if an alarm condition exist.
Alarm Silencing Relay
Two ________ relays are installed in the control panel. They are electrically connected to the water level control circuits to prevent short cycling of the controls do to changes in water level due to ship’s motion.
Adjustable Time Delay Relays
If at anytime during operation, a low water condition is indicated the _________ work to secure the burner.
Time Delay Relays