Codes & Regulations Flashcards

1
Q

Accessible Parking

A

2010 ADA standards and local codes determine the number of accessible parking spaces based off the total number of parking spaces available
Located close to the building and marked with the intl symbol for accessibility;
Should be adjacent to an accessible aisle; 5’ wide standard, 8’ wide for van
a percentage of accessible spaces may be required to be van, max slope of 2% maintained
Spaces are 8’W; is a 5’ aisle is used with a van, the space must be 11’W
Ramp not allowed with van spaces

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Fire resistance rating

A

the length of time that the item can withstand a standardized fire resistance test
building codes specify the min fire-resistance ratings the building elements must have in various circumstances

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Fire dampers

A

device installed in ducts and air transfer openings that is designed to automatically close on detection of heat to resist the passage of flame

Duct penetrations through fire resistant barriers are protected with fire dampers placed in line with the wall

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Smoke dampers

A

device installed in ducts and air transfer openings that are designed to resist the passage of smoke

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Fire partitions

A

a wall assembly with a 1-hour fire-resistance rating; must be continuous; used in the following designated locations:
-walls separating dwelling units
-Walls separating guest rooms in Group R-1 (hotels), R-2, and I-1 occupancies
-Walls separating tenant spaces in covered and open malls
-corridor walls
-elevator lobby separation for Groups I-2, I-3, and high-rise buildings and elsewhere required by the code

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Openings in fire partitions

A

must have a min rating of ¾ hours, except for corridors, which must be protected by 20-min fire-protection assemblies

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Fire barrier

A

a vertical or horizontal assembly that is fire-resistance rated and designed to restrict the spread of fire, confine it to limited areas, and/or afford safe passage for protected egress; must be continuous; must be greater than 1 hour rating; usually offers more protection that a fire partition; used to:
-enclose vertical exit enclosures, exit passageways, horizontal exits, and incidental use areas
-separate different occupancies in a mixed occupancy situation
-separate single occupancies into different areas
-otherwise provide a fire barrier where specifically required by a code provision in the IBC as well as the other international codes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

In fire barriers openings are limited

A

max aggregate width of 25% of the length of the wall, single openings cannot exceed 156 SF; unless both fire areas are sprinklered or they are fire doors serving an exit enclosure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Fire wall

A

a fire resistance rated wall this is used to separate a single structure into separate construction types or to provide for allowable area increases by creating what amounts to separate buildings even though they are attached; must extend from the foundation through the rood; must be 2-4 hour resistance; built so that one side can collapse and not affect the wall or adjacent building

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Smoke barrier

A

continuous vertical or horizontal membrane with a min fire-resistance rating of 1 hour that is designed an constructed to restrict the movement of smoke; passive; openings at least 20 min rating

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is considered a finish

A

textile wall and floor coverings, wainscoting, paneling, heavy wall covering, those applied structural or for decoration, acoustical correction, surface insulation, or similar purposes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Finishes rated according to ASTM E84

A

Class I are more resistant to flame spread than Class II; Class I would be used in vertical exits, exit passageways, exit access corridors in Groups I-1, I-2, and I-3 occupancies; if sprinklered Class II are allowed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Combustible decorative materials are limited

A

to 10% of the specific wall or ceiling area to which the material is attached, except in A occ where up to 75% is allowed if sprinklered and in Group R-2 where up to 50% is allowed if sprinklered

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Determining the occupancy group is the first step in the code analysis process

A

Assembly
+ A-1: with fixed seating for viewing of movies theaters, live performance
+ A-2: for food and drink consumption
+ A-3: for worship, recreation, etc. not classified elsewhere
+ A-4: for viewing of indoor sports
+ A-5: for outdoor sports
Business (B) for office or service transactions
Educational (E) > 5 people through 12th grade
Factory and Industrial
+F-1: moderate hazard
+F-2: low hazard
Hazardous (H)
Institutional
+ I-1: > 16 ambulatory people on 24 hour basis
+I-2: medical care on 24 hour basis
+I-3: > 5 people restained
+I-4: daycare for > 5 adults or infants (<2.5 yr)
Mercantile (M)
Residential
+ R-1: for transient lodging
+R-2: with 3 or more units
+R-3: 1 or 2 dwelling units with attached uses or child care < 6, less than 24 hours care
+R-4: residential assisted living where number of occupants >5 but < 16
Storage (S)
Utility (U)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Mixed occupancy

A

When a building or area has 2 or more occupancies

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Occupancy separation

A

IBC Table 508.4 shows required occupancy separations ranging from 1-4 hours; its a possible a fire-rated partition is not required between occupancies if the building is fully sprinklered

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

If storage is less than 100 SF

A

It is classified as an accessory to main occupancy

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Accessory occupancies

A

-A space or room that is ancillary to a main occupancy but that does not exceed 110% of the floor area of the story in which it is located
-does not need to be separated by a fire barrier
-exceptions: live/work units, most Group H occupancies, dwelling units in Group I-1, R-1, R-2, and R-3 occupancies must be separated from other units

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Incidental uses

A

Ancillary to a main occupancy and has the same classification as the nearest main occupancy, but poses a greater level of risk than that occupancy
must be separated form the main occupancy by a fire barrier, be sprinklered, or both
cannot exceed 10% of the area of the story on which it is located

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

Classification of construction type based on

A

the fire-resistance rating of the major construction components, including structural frame, bearing walls, exterior and interior non bearing walls, floor construction, and roof construction

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

What limits the area and height of a building

A

Construction type and occupancy groups

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Noncombustible types

A

Types I and II

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Combustible types

A

Types II, IV, and V

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Most and least fire restrictive types

A

Type I most
Type V least

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

Fire Zones

A

areas the local government may divide the city into representing the degree of fire hazard

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

Fire Hazard

A

based on density, access for fire fighting equip, existing building heights, etc; the most hazardous are classed as fire zone 1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

Allowable Height

A

-Chapter 5 of IBC
-Determined by the construction type, occupancy, and sprinklers
-the more hazardous a building is the smaller it should be to make it easier to egress and fire rescue

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
28
Q

Allowable floor areas

A

Determined by the construction type, occupancy, and sprinklers, and the amount of building frontage on a public way or open space

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
29
Q

Area factor increase based on frontage

A

If at least 25% of the building’s perimeter is located on a public way or open space, the basic allowable area may be increased; the open area must be on the same lot or dedicated to public use, and accessible from a street or fire lane

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
30
Q

public way or open space must be 20’ wide from the building face to:

A

-the closest interior lot line
-the entire width of the street, alley, or public way
-the exterior face of an adjacent building on the same property

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
31
Q

Mixed occupancy group

A

when the area of each separated occupancy is expressed as the ratio of its actual building area to its allowable building area, the sum of the ratios in each story must not be greater than 1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
32
Q

Fire walls can be used to separate occupancies when?

A

when max allowable floor area is reached in an existing building that is changing occupancy

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
33
Q

Location of Property

A

IBC Section 602
determined by specifying the fire resistance of exterior walls based on distance from property lines or adjacent building

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
34
Q

Means of egress

A

a continuous and unobstructed path of vertical and horizontal egress travel from any point in a building or structure to a public way

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
35
Q

Means of egress consists of 3 parts

A

The exit access
The exit
The exit discharge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
36
Q

The exit access

A

may or may not be protected; may include rooms, spaces, aisles, intervening rooms, hallways, corridors, ramps, and doorways; where travel distance is measured and regulated

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
37
Q

The exit

A

the portion that provides a protected path of egress between the exit access and exit discharge; fully enclosed and fire rated; travel distance not an issue once the exit path has been reached

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
38
Q

The exit discharge

A

between the termination of the exit and the public way; usually exterior elements and oaths; can include building lobby of multistory building

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
39
Q

Occupant load is established by taking the largest number determined by one of 3 methods

A

Occupant Load by Actual Number
Occupant Load by Table
Occupant Load by Combination

40
Q

Occupant load by actual number

A

usually only used in spaces with fixed seating so you can literally count the number of people that can be in a space

41
Q

Occupant load by table

A

calculate the area in SF assigned to a particular function and divide by an occupancy load factor as given in the code (table 1004); most common method
+gross floor area includes stairs, corridors, toilet rooms, mech rooms, closets, and interior partition thickness
+net floor area includes only the space actually used by the occupant

42
Q

Occupant load by combination

A

when an occupant load form an intervening space or accessory area exits through a primary space, the egress facilities from the primary space occupant load must include the occupant load of the primary space plus the occupant load of the intervening or accessory space

43
Q

Required number of exists

A

at least 1 exit required, 2 or more exits when the occupant load of a space or the common path of egress travel exceeds the numbers given in table 1006

44
Q

Common path of egress travel

A

-The portion of the exit access travel distance measured from the most remote point within a story to the point where the occupants have separate access to 2 exits of exit access doorways and can make a choice about which direction to go
-even if occupant count is smaller than counts given in table 1006, if exit travel path is exceeded more than 1 exit is required

45
Q

Separation of exits

A

When 2 doors are required in a non-sprinklered building, they must be not less than ½ the length of the max overall diagonal dimension of the building or area to be served; if sprinklered, the distance is reduced to ⅓ of the overall length; if 3 exits required, 2 must follow the above rule and the other must be accessible if one of the 2 becomes blocked

46
Q

Width of exits

A

-Stairways factor of .3”; .2” if the building is fully sprinklered and fire alarmed
-doors factor of .2”; .15” if the building is fully sprinklered and fire alarmed

47
Q

Egress can pass through an adjoining or intervening space if these 3 conditions are met:

A

-one of the 2 rooms or spaces is an accessory to the other
-neither room or space is a Group H occupancy
-there is a discernible path of egress travel to an exit

48
Q

Egress cannot pass through

A

kitchens, storerooms, closets, or spaces used for similar purposes, nor through any room that can be locked to prevent egress

49
Q

Size of a corridor is determined by

A

by multiplying the occupant load by the appropriate factor; must not be less than 44”

50
Q

Required width may not be reduced except in the following ways

A

-a door fully open may not project more than 7”
-handrails may not reduce the width more than 4.5” on each side
-trim and other decorative materials may not reduce the width more than 1.5” each side
-light fixtures and furnishings may not project more than 4” between the heights of 27” and 80” AFF

51
Q

Corridors must be fire-resistance rated and constructed as fire partitions except in one of the following exceptions:

A

-Group E occupancies where classrooms and assembly rooms have half their required egress leading directly to the exterior at ground level
-corridors in a dwelling unit or a guest room in a Group R occupancy of sleeping unit in Group I-1 and Group R occupancies
-corridors in open parking garages
-Group B occupancies that require only one exit by other provision in the code

52
Q

The level of safety the occupant is under when entreating a corridor must persist until exit

A

egress from the corridor must not pass through intervening rooms unless its a lobby, foyer, or reception room basically constructed as an enlarged version of the corridor

53
Q

A dead end corridor

A

Exists when a person is in a part of a building that requires 2 means of egress but has only one choice of direction that leads to an exit access doorway or an exit
Is limited to 20’

54
Q

Clear width of doors

A

-must always be 32” min; measured between the face of the door and the doorstop when the door is 90 degrees; door width is actually 36”
-min width must be sufficient for the occupant load served
-max width is 48”

55
Q

Door swings

A

-must swing in the direction of travel if occupant load is 50 or more
-Doors must be recessed if swinging into corridors

56
Q

Interior exit stairways

A

Must be completely enclosed

57
Q

4 or more story interior exit stairway

A

2 hour rating walls
1.5 hour rating doors

58
Q

Less than 4 story interior exit stairway

A

1 hour rating walls
1 hour rating doors

59
Q

All stairways width requirements

A

-Serving 50 or more occupants must be 44” wide min or the width determined by multiplying occupant load by the egress factor, whichever is larger
-less than 50 occupants must be 36” min

60
Q

Handrails for stairways

A

-if accessible means of egress, 48” min between handrails
-handrails may project into the required width 4.5”
-handrails on both sides, if more than 5’ wide an intermediate handrail is required; between 34-37” from tread, 12” extensions; 1.5-2” thick, not less that 1.5” from wall

61
Q

Landings for stairways

A

at top and bottom and not less than the width of the stair but not more than 48” if the stair is a straight run; 12’ max vertical distance between landings

62
Q

High-rise buildings

A

-Occupied floors more than 75’ above the lowest level of fire department vehicle access
-sprinklered, smoke detectors and alarms, communication systems, a central control station for fire department use, smoke control for exit stair enclosures, and standby power systems

63
Q

Guards

A

Must be 42” high; 4” sphere can’t pass through

64
Q

Floor area ratios

A

-The ratio of the gross floor area within a structure to the area of the lot on which the structure is situated
-must be developed with regard to setbacks

65
Q

Bulk plane restrictions

A

Establishes an imaginary inclined plane beginning at the lot line of the center of the street at a given elevation and slopes at a prescribed angle toward and over the lot, of which the building cannot cross

66
Q

Variance

A

Permission to deviate from the zoning regulations when zoning restrictions create undue hardships or the zoning ordinance does not completely cover unusual conditions

67
Q

Conditional use permit

A

allows a nonconforming use or other use in the zoning ordinance if the property owner meets certain conditions

68
Q

Accessible routes

A

-should be as close to general routes as possible
-5’ turning radius, if circle can’t be provided use a T-shape 36” min
-corridors 36” wide and min 32” at doors/passages which can’t be more than 24” long
-2 wheelchairs need 60”

69
Q

Toilet rooms turning space

A

can overlap with the required clear floor space at fixtures and controls and with the accessible route

70
Q

Turn in corridors or around obstructions

A
71
Q

Reach ranges when forward reach is unobstructed

A

high reach is 48”, low reach is 15” min

72
Q

Reach ranges when forward reach is obstructed

A

high reach is 44” when over 20-25”

73
Q

Reach ranges when clear floor space allows parallel approach

A

side reach is 48” max; if there’s an obstruction the reach is the same if the obstruction is 10” max depth and 34” max height

74
Q

Doorways is sufficient door clearance is not provided

A

Power assisted mechanisms must be installed

75
Q

Maneuvering Clearances at single doors

A
76
Q

Maneuvering clearances at double doors

A
77
Q

Opening force for doors

A

cannot be more than 5 pounds of force per foot max

78
Q

Accessible hardware

A

-Thresholds cannot exceed ¼”
-if ¼” rise is exceeded, for every ¼” over the first ¼” there must be a slope out ½”
-round doorknobs not allowed
-Hardware not mounted more than 48” aff
-closers should slow closing time

79
Q

Toilet stall accessibility

A

-door swings out away from toilet
-1 ambulatory stall where there are 6 or more toilet/urinal fixtures
-clearance depth depends on wall hung vs floor mounted toilet
-typical, 60” width, 56” depth, toilet is 16-18” on center from stall wall

80
Q

Grab bar mounting height

A

33-36” aff

81
Q

Toilet stall clearances

A
82
Q

Urinals

A

Elongated rim at 17” max aff and 13.5” min depth
clear floor 30” x 48”
urinal shields not extending beyond face of rim can have 30” clearance between them

83
Q

Accessible Lavatories and sinks

A

-If pipes are exposed they must be insulated
-faucets operable by one weak hand
-mirror bottoms 40” max from floor
-max depth of sink bowl is 6.5”

84
Q

Accessible lavatories and drinking fountain clearances

A
85
Q

Accessible drinking fountains

A

IBC requires 2 fountains, 1 for wheelchair users and 1 for standing users

86
Q

Clear floor space at accessible bathtubs

A
87
Q

Grab bars at accessible bathtubs

A

One located 9” above top of bathtub
The rest located 33-36” AFF

88
Q

Accessible showers

A

-In hotels and other suite/room type facilities a certain number of roll in showers must be provided
-permanent seat in smaller configuration, foldaway seat in the larger
-36” x 36” min for smaller with clear space 36” deep 48” wide
-30” x 60” min for larger with clear space 36” deep and 60” wide

89
Q

Accessible floor surfaces

A

-Stable, firm, and slip resistant
-if elevation change is ¼” - ½” it must be beveled with slope no greater than 1:2
-if elevation change is greater than ½” it must be accomplished with a ramp

90
Q

Accessible ramps

A

-Slope cannot be greater than 1:12
-max rise 30”
-if existing conditions prevent 1:12 , 1:10 can be allowed if the rise does not exceed 6”; 1:8 is allowed if the rise does not exceed 3”
-min clear width 36”; landings as wide as the ramp
-Landing length 60”
-handrails required if ramp is greater than 72” long and 6” high

91
Q

Accessible stairs

A

-max riser for stairs 7”, min tread 11”; open risers not allowed
-if stair is considered part of the accessible route, clear width between handrails must be 48”; area of refuge must be provided to accommodate a wheelchair space of 30” x 38” for each 200 occupants; area of refuge not required if building is sprinklered

92
Q

Protruding objects

A

-cannot reduce the clear width required for an accessible route
-an object can protrude from the wall any width so long as the clear width is maintained and it is a max of 27” aff
-Vertical clearance cannot be reduced to less than 80”, otherwise a guardrail must be provided

93
Q

Detectable warnings

A

-A surface feature to warn of hazards on a circulation path
-truncated domes .2” in height, spaced 1.6”-2.4” oc in a grid pattern
-24” continuous strips at open edges

94
Q

Accessible signage and alarms

A

-Signage for visually impaired required
-signage at elevators
-emergency warning systems should be visual and audible
-ADA requires accessible symbols at certain accessible rooms and features
-permanent indication signs for rooms; letters in uppercase ⅝”-2” high and 1/32” deep with braille
-directional and informational signs; letters in upper or lowercase ⅝”-3” high
-international symbol for accessibility at parking spaces, passenger loading zones, accessible entrances, and toilet and bathing facilities when not all are accessible

95
Q

Accessible telephones

A

-If public telephones provided, one is required on each floor to comply with ADA requirements
-TDD telecommunication device for the deaf

96
Q

Accessible seating

A

-If fixed or built in seating or tables in a common use area, at least 5% and no fewer than 1 of the seating areas must be accessible
-seats must include a companion seat and be located on a means of egress path
-at tables provide the standard 30” x 48” space, but a front approach table allows 17”-25” of the 48” length to be under the table, and at a side approach 19” of the 48” length can be under the table

97
Q

Accessible elevators

A

-Call button 48” max aff
-hall lantern 72” min aff; visual and audible
-raised and braille floor designation sign on each side of the elevator 60” aff
-floor buttons 48” max aff; unless serves more than 16 openings, 54” max aff