Code Requirements, Laws, Standards, and Regulations Flashcards
1003.2 ceiling height - egress
not less than 7’-6” AFF
1003.3 protruding objects on circulation path
MUST NOT reduce min. clear width of accessible route
Objects on wall between “ __-__ “ AFF must not protrude more than “___” into egress path of travel
27” - 80”
4”
Must not exceed 100’
The path of egress travel
Path of egress travel must not pass
through secondary space that is subject to closure by doors
Doors opening from occupied spaces into path of egress travel shall not project more than “___” into the required width
7”
Pivot or side-hinged doors shall swing “___ __ ____” of egress travel where serving a room/area w/occupant load of 50+
into the direction
Exit acess
the access to an exit
Common path of egress travel
portion of “exit access” that must be traversed BEFORE 2 separate paths of travel to 2 exits are available
travel distance
< 250’ along path of travel
measured from most remote point to centerline of exit
Table 1004.5
Maximum floor area allowance per occupant
Assembly - Unconcentrated (tables + chairs) — 15 net
Business areas — 150 gross