Code Mod 1-3 Flashcards
What is the identified Conductor?
White or grey wire acting as a grounded conductor returning the circuit current back to the source (think Neutral)(Not called Neutral)
Which Tables are used for the ampacities of a COPPER conductor(s)?
Table 1 for single conductors
Table 2 for no more than 3.
What Tables are used to Calculate the ampacities of an ALUMINIUM conductor(s)?
Table 3 for single conductors
Table 4 for no more than 3
What is the Termination temperature if the conductor is not marked, and has over 100 Amps? What is the min
size rating of AWG wire?
75°C, No. 1 AWG or larger
What is the Termination temperature if the conductor is not marked, and has less than 100 Amps? What is the max size rating of AWG wire?
60°C, No.1 AWG or smaller
What is the default Ambient Temperature if not stated?
30°C
What Tables do you use when dealing with equipment wire or flexible cable?
Table 11 and 12
According to Rule 4-010 Flexible Cords and equipment wire should be no smaller than_____AWG. Unless it’s ______ size_____, or _______ size______.
No. 18 AWG
Tinsel Cord, No. 27 AWG
Equipment cords for specific devices, No. 20 AWG
RULE 4-010
What are the Colours for a 3- phase set and what rule is it found under?
Red, Black, Blue, Neutral/ White
Rule 4-302
What rule do you find the percentile correction factors, for insulated conductors?
Rule 4-012
What Section of the CEC book would you find information on, Flexible Cables?
Section 12
What Table would you use for checking the Allowable Ampacities of Equipment/ Flexible Wire?
Table 12
What Table would you use to Check the Conditions of use for Flexible cords and Equipment wire?
Table 11