Q

What is the relationship between the opening time of an overcurrent device and the magnitude of ground fault current?

A

Inversely proportional. Higher current will cause device to operate more quickly.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Grounding functions to stabilize the _____ during normal operations by providing a _____.

A

Voltage-to-ground.

Common reference point.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

System bonding jumper size is based on the rating of _____.

A

The overcurrent device protecting the ungrounded conductors.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Table for selecting conductor size for concrete encased electrode.

A

Table 43

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

A fuse’s interrupting rating indicates it’s capability to safely open a circuit during a short circuit condition, true or false.

A

True. Rating correlates with possible fault current delivered from the source.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

A fuse rated for up to 60 amps is usually of _____ type construction

A

Barrel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Fuses 70 - 600A are of a _____ type.

A

Blade

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How does a trip-free breaker work?

A

It will trip under short circuit conditions even if holding the handle “on” (closed).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

A class A GFCI opens a circuit under what conditions?

A

If the leakage current is 6mA (0.006) or more

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What type of utility system is common in downtown core areas? How does that system operate?

A

Network system. Transformers are connected parallel on secondary.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the conventional type of utility system?

A

Radial system.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

If the ungrounded circuit conductor touches the grounded circuit conductor on the load side of the receptacle, will the GFCI receptacle open the circuit?

A

Yes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Should the secondary of a current transformer be fused?

A

No - OC protection is not required and the secondary must not be fused due to the possible high voltage induced by opening the circuit.