Cladding And Lagging TQ Prep Flashcards
What is the discharge angle of a gooseneck ventilator?
135°
What is the minimum height of the bottom straight section of a gooseneck ventilator above the base of a roof in heavy snowfall areas?
18”
What provides the main protection against rain, snow, and ice accumulation on the roof?
Roof curbs placed around the opening of the roof.
How often is the Alberta Building Code (ABC) republished?
Every 4 years.
What guidelines does the Alberta Building Code refer to?
SMACNA guidelines.
What are louvres designed to do?
Provide airflow into a building while keeping out moisture, birds, and insects.
What type of louvre blades are better at removing excess moisture?
Blades designed with a profile shape that has extra bends or folds.
How is the gooseneck ventilator hood attached?
It includes a straight section of duct that is fastened mechanically to the curb and sits 12” above the curb flashing.
What finishes can rolls of stainless steel cladding be ordered with?
Stucco embossed, smooth, 3/16” corrugated, or corrolon.
What are Pressed Elbows sized to cover?
Insulated 90° and 45° elbows.
What is the minimum lap for covering pipe insulation with aluminum?
50mm (2”) minimum.
Where should the lap for cladding on a horizontal pipe be placed?
Away from prevailing winds at 2 O’ clock.
What is the purpose of moisture barriers applied to aluminum?
To provide protection against corrosion.
Why can stainless steel cladding be used instead of aluminum?
For chemical and fire resistance.
How should aluminum be fastened on insulated tanks with excessive expansion and contraction?
With steel bands and expansion springs.