Chiefs Reg 4 Flashcards
How often is a reg 4 required ?
Every 5 years or 1 year depending on what is getting checked
How many reg 4’s are retained?
The last 2
What is a class I system ?
Standpipe system primarily for FD use
What is a class II system ?
Standpipe system for use of building occupant until FD arrives
What is a Class III system ?
For use of either building occupant or FD (combination)
What is a combined system?
Water piping serving both 21/2” outlets for FD use
How often are central signaling systems , fire escape assemblies and automatic elevators tested ?
Annually
How many PSI is the air test that is given to dry standpipes before hydrostatic tests?
25 PSI
What is the max allowable pressure lost in dry standpipes due to friction loss ?
No > 15 PSI
How much pressure for a hydrostatic test is required in a class I standpipe?
- at least 50 psi more than head pressure
- no less than 200 PSI
When an automatic sprinkler system is activated , an outside bell will ring within how many seconds of activation ?
90 seconds