Chapters 3 (Definitions) Flashcards
NFPA Definitions, Sprinkler System Types, System Components, Sprinkler Types, Construction Definitions, Supply Piping Definitions, Hydrant Definitions, Storage Definitions, Marine Definitions, Hanging & Bracing Definitions
Acceptable to the authority having jurisdiction.
Approved
3.2.1
An organization, office, or individual responsible for enforcing the requirements of a code or standard, or for approving equipment, materials, an installation, or a procedure.
Authority Having Jurisdiction (AHJ)
3.2.2
Equipment, materials, or services included in a list published by an organization that is acceptable to the authority having jurisdiction and concerned with evaluation of products or services, that maintains periodic inspections of production of listed equipment or materials or periodic evaluation of services, and whose listing states that either the equipment, material or service meets appropriate designated standards or has been tested and found suitable for a specified purpose.
Listed
3.2.3
Indicates a mandatory requirement
Shall
3.2.4
Indicates a recommendation or that which is advised but not required.
Should
3.2.5
An NFPA Standard, the main text of which contains only mandatory provisions using the word “shall” to indicate requirements and that is in a form generally suitable for mandatory reference by another standard or code or for adoption into law.
Standard
3.2.6
A fire suppression or control device that operates automatically when its heat-activated element is heated to its thermal rating or above, allowing water to discharge over a specified area.
Automatic Sprinkler
3.3.1
An architectural ceiling feature that consist of a bounded area of ceiling located at a higher elevation than the attached lower ceiling.
Ceiling Pocket
3.3.4
Any ceiling system installed in the same plane with horizontal openings to the structure to above on all sides.
Cloud Ceiling
3.3.5.1
A continuous ceiling an a single plane.
Flat Ceiling
3.3.5.2
A ceiling with a slope not exceeding 2 in 12.
Horizontal Ceiling
3.3.5.3
A ceiling with a slope exceeding 2 in 12.
Sloped Ceiling
3.3.5.4
A continuous ceiling free from significant irregularities, lumps, or indentations.
Smooth Ceiling
3.3.5.5
A space completely enclosed by walls and a ceiling. Each wall in the compartment is permitted to have openings to an adjourning space if the openings have a minimum lintel depth of 8” from the ceiling and total width of the openings in each wall does not exceed 8 ft. A single opening of 36 inches or less in width without a lintel is permitted when there are no other openings to adjoining spaces.
Compartment
3.3.6
A valve controlling flow to water-based fire protection systems and devices.
Control Valve
3.3.7
A continuous material protruding downward from the ceiling to create a reservoir for collecting smoke and heat.
Draft Curtain
3.3.8
A suspended ceiling system, which is installed below the sprinklers, with listed translucent or opaque panels that are heat sensitive and fall from their setting when exposed to heat.
Drop-out ceiling
3.3.9
Limiting the size of a fire by distribution of water so as to decrease the heat release rate and pre-wet adjacent combustibles, while controlling ceiling gas temperature to avoid structural damage.
Fire Control
3.3.11
Sharply reducing the heat release rate of a fire and preventing its growth by means of a direct and sufficient application of water through the fire plume to the burning fuel surface.
Fire Suppression
3.3.12
A ceiling fan that is approximately 6 ft to 24 ft in diameter with a rotational speed of approximately 30 to 70 revolutions per minute.
High Volume Low Speed Fan
3.3.14
A calculated sprinkler system in which pipe sizes are selected on a pressure loss basis to provide a prescribed water density, in gal/min per sq ft, or a prescribed minimum discharge pressure or flow per sprinkler, distributed with a reasonable degree of uniformity over a specified area.
Hydraulically Designed System
3.3.15
A compartment of light hazard occupancy classification having unobstructed construction and a floor space not exceeding 800 sq ft
Small Room
3.3.22
A system that consists of an integrated network of piping designed in accordance with fire protection engineering standards that includes a water supply source, a water control valve, a waterflow alarm, and a drain.
Sprinkler System
3.3.23
The maximum anticipated static (nonflowing) or flowing pressure applied to sprinkler system components exclusive of surge pressures and exclusive of pressure from the fire department connection.
System Working Pressure
3.3.24
A wet pipe system using automatic sprinklers that contain a liquid solution to prevent freezing of the system, intended to discharge the solution upon sprinkler operation, followed immediately by water from a water supply.
Antifreeze Sprinkler System
3.4.1
A wet pipe sprinkler system having non-fire protection connections to automatic sprinkler systems in a closed-loop piping arrangement for the purpose of utilizing sprinkler pipe to conduct water for heating and cooling, where water is not removed or used from the system but only circulated through the piping system.
Circulating Closed-Loop Sprinkler System
3.4.2
A sprinkler system employing automatic sprinklers attached to a piping system containing air under pressure with a supplemental detection system installed in the same area as the sprinklers. Operation of the detection system actuates tripping devices that open dry pipe valves simultaneously and without loss of air pressure in the system. The detection system also serves as an automatic fire alarm system.
Combined Dry Pipe-Reaction sprinkler System
3.4.3
A sprinkler system employing open sprinklers or nozzles that are attached to a piping system that is connected to a water supply through a valve that is opened by the operation of a detection system installed in the same area as the sprinklers or the nozzles. When this valve opens, water flows into the piping system and discharges from all sprinklers or nozzles attached to the system.
Deluge Sprinkler System
3.4.4
A sprinkler system employing automatic sprinklers that are attached to a piping system containing air or nitrogen under pressure, the release of which (as from a sprinkler) permits the water pressure to open a valve known as a dry pipe valve, and the water then flows into the piping system and out the opened sprinkler.
Dry Pipe Sprinkler System
3.4.5
A sprinkler system in which parallel cross mains are connected by multiple branch lines, causing an operating sprinkler to receive water from both ends of its branch line while other branch lines help transfer water between cross mains.
Gridded sprinkler System
3.4.6