Chapter 5 Flashcards

1
Q

name a document that can assist in determining if an assembly is two hour rated

A

UL Fire resistance directory

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

a firestopping material that expands when heated is referred to as

A

intumescent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

power limited equipment is determined to meet the limitations by______

A

the manufacture

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

a cable tray is considered a ______penetration

A

dynamic

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Power limited wiring requirements are found in part ______ of article 760

A

3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

the location of unit resistances for copper wire is found in _____ of the NEC

A

table 8

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

NEC ______ requires electrical penetrations to be firestopped

A

300.21

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

assuming that there are no approved separations between conductors, which of the following conductors are permitted in the same cable or raceway as power limited circuit conductors?

A

class 2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

a firestopping classification having a minimum f rating of _____ must be used on a two hour rated firewall to resist the passage of flames

A

120

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Which article of the NEC covers burglary system wiring

A

Article 725

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

non power limited circuits may be wired using what methods

A

ch3

non power limited methods

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

what cable is suitable for two hours of direct attack by fire

A

mineral insulated

circuit integrity

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

where non-power-limited wiring is installed exposed, it must be mechanically protected within _____ of the finished floor.

A

7 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Table provide limitations for power limited circuits

A

12A and 12 B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

the inside of a conduit installed under a concrete slab at grade level is considered a ____ location

A

Wet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

18 AWG uncoated solid copper has a unit resistance of ____ ohms per 1000 ft

A

7.77