A general use snap switch shall be connected to no more than _____ percentage of its rated use?
80%
What color triangle marking will be on a noise cancelling outlet?
Orange🍊
Light poles shall have a hand hole of not less than ______?
2”x4”
What is the minimum space between a recessed fixture and thermal insulation?
3”
A furnace has to be run on what type of circuit?
Individual branch circuit
Electrically operated kitchen waste disp shall be permitted to be cord and plug connected with a flexible cord not more than how many inches and not less than how many inches?
36 inches, not less than 18 inches
What type of cable does a garage disposal cord have to be made of?
Listed for use
Branch circuits supplying two or more outlets for fixed electrical space heating equipment shall be rated for not over how many amps?
30 amps
A conductor supplying a single motor used in continuous duty application shall have a ampacity of percent of the motors FLC?
125%
Conductors supplying several motors shall have a ampacity of not less than the sum of the motors plus ____ percent of the highest rated motor?
25%
Fuses are out on the current carrying conductors as well as the grounded conductor if it is what type of motor feeder?
3 wire/3 phase
By what percent is the FLC of a wound rotor multiplied, to determine the motors minimum OCPD using inverse time breaker?
150%
Disconnecting means for the motor circuits rated 600 volts, or less shall have an ampere rating not less than ___ percent of the FLC rating?
115%