CHAPTER 3- BASIC COMMERCIAL OCCUPANCY Flashcards
Inspection cycle for one exit
3 years
Inspection cycle for two or more exits
Annual
Portable fire extinguishers gross weight not exceeding __ pounds shall be installed so the top of extinguisher is not more than __ feet above the floor
40
5’
Portable extinguishers greater than 40 pounds shall be installed that the top of the extinguisher is not more than ___ feet above the floor
3 1/2’
In no case shall the clearance between the bottom of the extinguisher and floor be less than __ inches
4
Special extinguishing systems shall be tested
semi annually
Pressurized cylinder shows a loss in net content weight of more than __ percent or drop in pressure of more than __ percent, shall be refilled/replaced
5
10
Copies of hazardous substances info forms shall be maintained for a period of not less than __ years
three
storage piles
floor area within a single storage area limited to ____ square feet
3000
An area of a building separated from other areas by division walls or occupancy separations and containing one or more storage piles.
Single Storage Area
main aisles
an unobstructed way of egress at least __ feet in width
8’
Side Aisles
an unobstructed way of egress not less than __ feet in width and transacting main aisles
4’