Chapter 3 Flashcards
Direct buried conductors and cables emerging from grade and specified in columns 1 and 4 of table 3.0.1.5 shall be protected by enclosures or raceways extending from the minimum cover distance below grade to a point at least ________ above finished grade. In no case shall the protection be required to exceed ______ below finished grade.
2500 mm, 450 mm
Underground service conductors that are not encased in concrete and that are buried 450 mm or more below grade shall have their location identified by a ________ that is placed in the trench at least ______ above the underground installation.
Warning ribbon, 300 mm
In both exposed and concealed locations, where a cable or a raceway-type wiring method is installed through bored hole in joists, rafters, ir wood members, holes shall be bored so that the edge of the hole is not less than _______ from the nearest edge of the wood member.
32 mm
The cable or raceway shall be protected from penetration by screws or nails by a steel plates or bushings, at least _______ thick, and of appropriate length and width installed to cover the area of the wiring.
1.6 mm
A cable, raceway, or box, installed in exposed or concealed locations under metal-corrugated sheet roof decking, shall be installed and supported so there is not less than ______ measure from the lowest surface of the roof decking to the top of the cable, raceway, or box.
38 mm
True or False.
A cable, raceway, or box shall not be installed in concealed locations in metal-corrugated, sheet decking-type roof.
True
Cable- and raceway-type wiring methods installed in a groove, to be covered by wallboard, siding, panelling, carpeting, or similar finish shall be protected by ______ thick steel plate, sleeve or equivalent or by not less than ______ free space for the full length of the groove in which the cable or raceway is installed.
1.6 mm, 32-mm
Where raceways contain _______ mm2 or larger insulated circuit conductors, and these conductors enter a cabinet, a box, an enclosure, or a raceway, the conductors shall be protected by an identified fitting providing a smoothly rounded insulating surface, unless the conductors are separated from the fitting or raceway by identified insulating material that is securely fastened in place.
22
Conduits or raceways through which moisture may contact live parts shall be sealed or plugged at either or both ends. Spare or unused raceways shall also be sealed. _______ shall be identified for use with the cable insulation, conductor insulation, bare conductor, shield, or other components.
Sealants
Where protected from corrosion solely by _________, ferrous metal raceways, cable trays, cablebus, auxiliary gutter, cable armor, boxes, cable sheathing, cabinets, metal elbows, couplings, nipples, fittings, supports, and support hardware shall not be used outdoors or in wet location.
Enamel
T or F
Support wires that do not provide secure support shall be permitted as the sole support.
F
T or F
Support wires and associated fittings that provide secure support and that are installed in addition to the ceiling grid support wired shall be permitted as the sole support.
T
At least _____ of free conductor, measured from the point in the box where it emerges from its raceway or cable sheath, shall be left at each outlet, junction, and switch point for splices or the connection of luminaires or devices.
150 mm
Where the opening to an outlet, junction or switch point is less than _______ in any dimension, each conductor shall be long enough to extend at least _______ outside the opening.
200 mm, 75 mm
FMC shall be permitted, in lengths not to exceed ______ to connect physically adjustable equipment and devices permitted to be in these fabricated ducts.
1.2 m (4ft)
Identification.
Electrical conduits, or other raceways round in cross section, that are suitable for use underground or embedded in concrete.
Electrical Ducts
Identification.
The heat transfer capability through a substance by conduction.
Thermal Resistivity
For other establishments, solid dielectric insulated conductor operated above ________ volts in permanent installation shall have ozone-resistant insulation and shall be shielded.
2000V
Conductors used for direct-burial application shall be of a type identified for such use. Cables rated above _______ shall be shielded.
2000V
Nonshielded multiconductor cables rated _________ shall be permitted if the cable has an overall metallic sheath or armor.
2001-2400V
Airfield lighting cable used in series circuits that are rated up to _______ and are powered by regulators shall be permitted to be nonshielded.
5000V
Cabinets and cutout boxes that contain devices or apparatus connected within the cabinet or box to more than ____ conductors, including those of branch circuits, meter loops, feeder circuits, power circuits, and similar circuits, but not including the supply circuit or a continuation thereof, shall have back-wiring spaces or one or more side-wiring spaces, side gutters, or wiring compartments.
8
T or F
Cabinets and cutout boxes shall be deep enough to allow the closing of the doors when 30-ampere branch-circuit panelboard switches are in any position, when combination cutout switches are in any position, or when other singe-throw switches are opened as far as their construction permits.
T
There shall be an airspace of at least _____ between the walls, back, gutter partitions, if of metal, or door of any cabinet or cutout box and the nearest exposed current-carrying part of devices mounted within the cabinet where the voltage does not exceed 250. This spacing shall be increased to at least _______ for voltages of 251-1000, nominal.
12.7 mm, 25.4 mm
Exception: Where the door is lined with an approved insulating material or is of a thickness of metal not less than _______ uncoated, the airspace shall not be less than 12.7 mm.
2.36 mm
There shall be an airspace of at least ______ between any live part, including live metal parts of enclosed fuses, and the door.
25.4 mm
Other than at points of support, there shall be an airspace of at least ______ between the base of the device and the wall of any metal cabinet or cutout box in which the device is mounted.
1.59 mm