Chapter 11 Surface Preparation Instrumentation Flashcards
1
Q
- Types of soluble salt contamination include:
A
Chlorides, Sulfates, Nitrates
2
Q
- If inspection is to be effective with regards to soluble salts, the specification should very clearly state:
A
- Limits of soluble salts to be accepted
- Type of salts to be limited on the substrate
- Test method to use
- Frequency of testing
- Where to administer tests
3
Q
- Test for soluble salts include:
A
- Potassium ferricyanide
- Bresle patch
- Sleeve test
- Soluble salt meters
- Conductivity
4
Q
- Depth of surface profile can be evaluated by several methods:
A
ISO comparators
Replica tape
Digital profile gauge
5
Q
- The ISO comparator grades may be recorded:
A
Finer-than-Fine Fine Medium Coarse Coarser-than-Coarse
6
Q
- The two types of replica tape that are commonly used:
A
Coarse (20 to 64 um) Extra Coarse (38 to 115 um)
7
Q
- List the standards for using the replica tape:
A
NACE Standard SP0287
ASTM D 4417
Method C
ISO 8503-5
8
Q
- When using replica tape common error include:
A
- Inherent variation in point-to-point profile over the surface being measured.
- Dirt particles on either the replica tape or gauge.
- Gauge accuracy.
- Rubbing technique. Either excessive or inadequate burnishing force.