Chapter 10 Flashcards
Article ____________ of the National Electrical Code covers installation of motor circuits.
430
Identify by letter the portion of the motor installation shown in Figure 8-1 that meets the purpose/requirement of the list provided.
picture overload is F disconnecting means is a control circuit protectionis C providing control circuit is e short circuit protection is b size of conductos is g controller is d
Motor branch circuit conductors must have an “ampacity” of not less than what percentage of the motor’s full-load current?
125 percent
The full-load current rating shown on the motor’s nameplate is not permitted to be used to determine the ampacity of the conductors.
True
The full-load current rating shown on the motor’s nameplate is permitted to be used to determine the overload protection for the motor.
True
According to the NEC, determine the minimum branch-circuit ampacity required for a 7 1/2 hp, 230-V, three-phase motor.
27.5 amps
A 20 hp motor and a 10 hp motor, both 460-V, three-phase, share the same feeder. Determine the minimum branch circuit ampacity required to size the feeder conductors.
47.75
For the motor branch circuit shown in Figure 8-2, state what undesirable operating condition each of the protective devices guards against.
a. short circuit and ground fault protection
b. overload protection
c. `control circuit over current protection
d. integral thermal protector
The starting current of a motor is approximately the same as its rated full-load current.
flase
With an inverse time circuit breaker, the higher the overcurrent, the longer the time required for the breaker to trip.
false
According to the NEC, what size of inverse time circuit breaker is permitted to be used for short-circuit and ground fault protection for a 5 hp, 230-V, three-phase squirrel-cage motor?
full load current FLC is 15.2
250 percent
38 amp inverse time circuit breaker
A motor overload condition is normally caused by
excessive motor load
Time-delay fuses provide both overload and short-circuit protection.
True
For any given horsepower motor, the nameplate full-load ampere rating is the same as that given in NEC tables. (True/Fa1se
False
In the majority of applications, motor overcurrent protection is provided by overcurrent _________________________ in the motor controller.
Relays
Motor control circuit conductors are not permitted to be tapped from the motor branch circuit conductors. (True/Fa1se)
False
Motor control circuits do not carry the main power current to the motor. (True/Fa1se) ____________
True
A motor ___________________________ is used to start and stop an electric motor by closing and opening the main power current to the motor.
controller
Which of the following is an example of a motor controller?
a. Magnetic starter
b. Manual snap switch
c. Adjustable-speed drive
d. All of these
All of these
The purpose of a motor _______________________________ means is to open the supply conductors to the motor, allowing personnel to work safely on the installation.
disconnecting
The disconnecting means for the motor controller and the motor must open all ________________________ supply conductors simultaneously.
Ungrounded
In general, each motor requires a disconnecting means that is located within sight of the motor. “In sight of” is defined as being visible, and not more than ________________ feet in distance from one another.
50 feet
An isolation switch should not be operated under load. (True/Fa1se) ____________
TRUE
Motor control circuits can be the same voltage as the motor up to 600 V, or can be reduced by means of a control ______________________ .
transformer
Where one side of the motor control circuit is grounded, the design of the control circuit must prevent the motor from being started because of a __________________ fault in the control circuit wiring.
groiund
All motors tend to draw much more current during the starting period than when rotating at operating speed. (True/Fa1se) ____________
True
The current that flows before a motor begins to turn is called its
a. Locked-rotor current b. Full-load current c. No-load current d. Rated current
locked rotor