Chapter 1: Apartments, Hotels, Condominiums and Apartment/Hotels & Chapter 2: MultiUnit Dwellings Flashcards
Provide and maintain appropriate numbers on a ________ background and visible from the street to indicate the correct address of the building
CONTRASTING
ADDRESS: Minimum size is _ inches high by __ inches wide.
4
2
ADDRESS *FORMULA: the height in inches shall be___of the distance in feet from the property line to the structure as seen from the street which the structure faces. The width of the numbers shall be___ of the height.
1/10th
1/2
The _____ shall be of a type approved by the Chief and shall contain all keys determined by the Chief to be necessary to gain access.
key box
All Fire Department sprinkler and standpipe inlet connections shall be provided with approved signs indicating the___ ____ _____ and the ____ ______. Signs shall be securely attached to the building adjacent to the inlet connections. Signs shall be not less than ___inches in width and ___ inches in height.
type of system & area served
8 width
4 height
Automatic sprinkler systems, standpipe systems, fire pumps, and risers shall be provided and maintained with identification signs for all ____, ____, ____, _______.
control, drain, test, and alarm valves.
Directional arrows shall be provided to indicate ____ _____ on fire pumps and risers.
water flow
Signs stating “______ _____-_____” showing the location of sprinkler shutoff valves shall be provided on doors of rooms or closets that contain sprinkler shutoff valves. Directional signs shall include an arrow indicating the _____ _____ _____ to sprinkler shutoff valves.
SPRINKLER SHUT-OFF
direction of travel
Fire hose cabinets shall be clearly identifiable or contain a sign on the cabinet door stating “____ _____” with letters not less than __ inches in height on a contrasting background.
FIRE HOSE
3 INCHES
Fire hose cabinets that contain a fire extinguisher shall also be identified with a sign stating “____ _________” with letters not less than __inches high on a contrasting background
FIRE EXTINGUISHER
3 INCHES
In the event an apartment house has __ or more dwelling units or a hotel has __ or more guest rooms, either the owner or a responsible resident having charge thereof shall reside on the premises.
16
20
The owner or manager of every apartment house in which there are 16 or more dwelling units and every hotel in which there are 20 or more guest rooms, shall, upon request of the Chief, furnish in writing the ____, _____ _____, ______ __________ of the current responsible resident. Such statement shall be signed by both the owner or manager and the responsible resident.
NAME, UNIT NUMBER, TELEPHONE NUMBER
If the owner does not reside upon the premises of any apartment house in which there are less than 16 dwelling units or any hotel in which there are less than 20 guest rooms, a notice stating the owner’s name and address, or the name and address of the owner’s agent in charge of the occupancy shall be what ?
posted in a conspicuous place on the premises.
“permanently wired’ smoke detectors be installed in multiple unit residential occupancies containing __ or more dwelling units.
2
Smoke Detectors shall be maintained in dependable operating condition and tested every _ _____ or as required by the Chief.
6 months
Fire assembly doors shall be kept in a _____ position and shall be equipped with an approved, listed ______-______ ______.
closed
self-closing device
Any person in charge or control of a building shall remove any block, wedge, or other device which is known by such person to be causing a self-closing fire assembly door to remain in an____ position.
open
All fire assembly doors shall have a_____ or other _________ showing the _____ _______ _______. Labels shall be approved and shall be permanently affixed at the factory. No person shall remove or otherwise obliterate the label or other identification showing the fire protection rating.
label or other identification
Fire Protective Rating
Fire hose shall be maintained in readiness for immediate emergency use in the following manner:
1) Hose shall be _____ in an approved manner.
2) Hose shall be _____ feet in length and in good condition.
3) A proper_____ shall be provided for the type of hose used. Unlined hose shall not be equipped with a nozzle ______.
4) All fire hose connections shall be provided with ________ _______ _________ hose coupling screw threads as specified in LAFD Standard No. 53.
- racked
- 100 ft
- nozzle/ shutoff
- American National Standard
Hose cabinets shall be maintained in good repair and shall only be used for housing of _____ & _______.
fire hose and portable extinguishers
Every rubbish chute shall terminate in a ______ ________ or approved _______ _________ outside of a building of sufficient capacity to receive the entire volume of hazardous refuse being dumped in the chute.
rubbish room or noncombustible container
An approved automatic or manually activated local fire alarm system shall be provided for:
A) Every apartment house ___ or more stories in height or containing ___ or more dwelling units.
B) Every hotel ___ or more stories in height or containing ___ or more guest rooms.
A) 3/16
B) 3/20
Fire Alarm Systems are not required:
1. In buildings which were constructed or converted to such use prior to what date ?
Sept.19, 1947
If a fire alarm system is found inoperative during a routine general, night or pre-fire plan inspection, issue _______________to the owner or responsible person, ordering that:
A) The fire alarm system shall be serviced and restored to full operation________(57.20.15).
B) If the system cannot be serviced and restored to full operation immediately, a ____ ______shall be established in accordance with Division 13 of the Fire Code until the system is restored to full operation (57.13.03).
C) The Department shall be notified when the system is ____ __ ____ _______(57.20.16).
FIRE/LIFE SAFETY VIOLATION (F340-C)
A) IMMEDIATELY
B) Fire Watch
C) Restored to FULL operation