ch 5 Flashcards

1
Q

The ? is/are defined as the conductors and equipment for delivering electric energy from the serving utility to the wiring system of the premises served.

A

service

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Where a system is grounded, the service must be supplied with a(n) ? conductor.

A

grounded

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the minimum-size aluminum main bonding jumper (wire-type) for a service if the largest ungrounded service conductor is 500 (kcmil) copper?

A

1/0 AWG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

The grounded conductor of a service must always be a neutral conductor.

A

false

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Where the utility transformer supplying a service is located outside the building, a grounding connection is not required to be made outside a building or structure served by a grounded electrical service.

A

false

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

A grounding electrode connection is required to be made at a(n) ? location anywhere from the load end of the overhead service conductors, service drop, underground service conductors, or service lateral up to and including the terminal or bus to which the grounded conductor is connected in the service disconnecting means.

A

accessible

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

A meter socket enclosure sealed by the utility makes the enclosure inaccessible, by definition.

A

false

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Which of the following is not one of the four conductors in the grounding and bonding scheme for a service supplied by a grounded system?

A

System bonding jumper

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where a service is supplied by an ungrounded system, the grounded conductor is required to be routed to the service disconnecting means enclosure and bonded to it.

A

false

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Where a service is supplied by a grounded system, the grounded conductor is required to be routed to the service disconnecting means enclosure and bonded to it.

A

true

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The grounded conductor is required to be routed to the service equipment along with its associated ungrounded service conductors.

A

true

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

The main bonding jumper in a service disconnecting means enclosure can be in which of the following forms?

A

Bus

Green screw

Wire

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

If a service disconnecting means is made up of six disconnects in separate enclosures, how many main bonding jumpers will be required for the service?

A

6

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Where the service disconnecting means is made up of two to six disconnects in a single listed service equipment assembly, how many main bonding jumpers are required within the listed assembly?

A

1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

If a main bonding jumper is a wire type, what NEC table is used to size it?

A

Table 250.102(C)(1)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

The grounded neutral conductor serves which two purposes for a grounded service?

A

Carries the maximum unbalanced return neutral load

Serves as an effective ground-fault current path in gro

17
Q

If a main bonding jumper is a screw, the screw is always required to be identified using the color green.

A

true

18
Q

The ? is a conductor connected to the neutral point of a system that is intended to carry current under normal conditions.

A

neutral conductor

19
Q

For a grounded service, the ? is the intentionally constructed, low-impedance, effective ground-fault current path addressed in 250.4(A).

A

grounded conductor

20
Q

If the ungrounded service conductors are 600 kcmil copper, what is the minimum size required for the grounded conductor supplying the same service?

A

1/0 AWG

21
Q

Where a service is supplied from a corner-grounded system, and the ungrounded conductors are sized at 750 kcmil copper, what is the minimum size required for the grounded conductor?

A

750 kcmil copper

22
Q

Where a grounded service is supplied using two 500 kcmil copper conductors in parallel (in two separate raceways) for each ungrounded service conductor, what is the minimum size required for the grounded conductor in each raceway supplying the service?

A

1/0 AWG

23
Q

Which of the following characteristics are required for ungrounded conductors installed in parallel?

A

Must be not smaller than 1/0 AWG (generally)

Must be the same conductor material

Must be the same insulation type

Must be the same length

Same size

Terminated the same

24
Q

Grounding connections to the grounded conductor are generally not permitted on the load side of the service equipment enclosure.

A

true

25
Q

A grounded conductor (often the neutral) larger than 6 AWG is required to be identified by which of the following methods?

A

A bare conductor that is part of a listed service-entrance cable assembly

A continuous white or gray outer finish

A distinctive white or gray marking at terminations that encircles the conductor

Three continuous white or gray stripes along its entire length on other than green insulation

26
Q

The service disconnecting means used for a grounded supply system is required to be listed as suitable for use as service equipment.

A

true

27
Q

Service equipment that is listed as suitable for use only as service equipment always includes a main bonding jumper.

A

false

28
Q

The NEC requires that a(n) ? be provided in the grounded conductor for service equipment.

A

disconnecting means

29
Q

If a service switchboard is supplied from an ungrounded 240-volt system, which of the following markings are required on the switchboard?

A

Caution: Ungrounded System Operating 240 Volts Between Conductors

30
Q

The NEC generally requires all metal enclosures and raceways for service conductors to be grounded except for metal components such as metal elbows in a run of nonmetallic service raceway that are isolated from contact by persons by not less than ? of cover to any part of the elbow.

A

18 inches

31
Q

Ground detectors are required to be installed on services supplied by ungrounded systems, and the ground detection sensing equipment must be connected as close as practicable to the service or source.

A

true

32
Q

If the size of the largest ungrounded service conductor for a service is 3,600 kcmil (six 600 kcmil conductors in parallel per phase), what is the minimum-size copper wire-type main bonding jumper required?

A

500 kcmil copper

Note: Review sizing methods for the 12.5% rule when the size of the largest ungrounded service conductor exceeds the values in Table 250.102(C)(1). Use of Table 8, Chapter 9 should be reviewed.

3600 x 12.5% = 450 kcmil

Take that value to Table 8 in the left column and find that the minimum kcmil required is 450 (larger than 400 kcmil), then round up to 500 kcmil copper.
The correct answer is: 500 kcmil copper

33
Q

Referring to the drawing, what is the minimum size required for a copper wire-type main bonding jumper for this service?

A

2 awg

34
Q

What is the minimum size required for a copper grounded conductor of a 3-phase, 3-wire, corner grounding delta system if the ungrounded phase conductors are sized at 500 kcmil copper?

A

500 kcmil

Note: Refer to Section 250.24(C)(3) to confirm the answer. The grounded conductor of this system must be not less that the size of the ungrounded conductors of this system.
The correct answer is: 500 kcmil

35
Q

Because in-ground swimming pools provide an excellent grounding connection to the Earth, when they are installed on a property, they are required to be included in, and bonded to, the grounding electrode system installed for a building or structure served.

A

false

36
Q

Where the utility transformer supplying the service is located outside the building or structure served, at least one additional grounding connection shall be made from the grounded service conductor to a grounding electrode at which of the following locations?

A

At the transformer

Elsewhere outside the building