CH. 16 Flashcards
The ____ is the value at which a device begins operation.
cut-in
A control system’s ____ is the set of numbers between and including cut-in and cut-out values.
range
In electronic controls, range adjustment is a function of the ____.
processor
A system’s ____ is the number of units between the cut-out and cut-in values.
differential
A device used to change one form of energy into another form is a ____.
transducer
The desired condition in a control system is called the ____.
set point
The difference between the desired condition and the present condition is called the ____.
offset
The present condition as measured by the sensor in a control system is the ____.
control point
Below-atmospheric-pressure elements ____.
contain volatile fluid in a partial vacuum
A bimetal coil ____ as the surrounding air gets warmer.
expands
Which of the following statements about electronic sensors is true?
They can accurately sense extremely high and low temperatures.
The sensing device is usually a thermistor.
Correct!
All of the above.
They operate at a low voltage.
All of the above.
When high head pressure in a hermetic system causes oil and refrigerant breakdown, the presence of moisture or dirt can result in ____ forming.
sludge
carbon
acids
Correct!
All of the above.
All of the above.
In a low-pressure motor control, the cut-out and cut-in pressures are set to maintain proper ____.
evaporator temperature
Which of the following statements about the terminals of a current relay is not true?
A current relay is wired by connecting an ungrounded wire to the M terminal.
Current relays are ____.
All of the above.
typically wired in series with the run windings
usually found on low-torque, single-phase motors
used to close and open the start winding circuit
All of the above.
The pickup voltage required to operate a potential relay is generated when a motor reaches around ____ of its normal operating speed.
3/4
Contactors with ____ of contacts are used to control three-phase motor operation.
three or four sets
After internal motor overload protection opens the motor circuit due to overheating, a technician should ____ to speed up compressor cooling.
use dry ice and forced air