CFAA Theory Questions Flashcards
The Emergency Voice Communication system
a. Does not deliver the Alert signal.
b. Are seldom required in a Building Code-defined “high” building.
c. Serves only those areas of a building open to the public.
d. Is intended to reduce panic in a fire emergency.
The technician knows that a conventional “Fixed-Temperature Only” detector cannot be tested with heat, and that such a detector will be recognized by :
a. A warning sign affixed to the ceiling adjacent to the detector.
b. A red dot on the detector’s air chamber
c. A blue dot on its heat-collecting fin.
d. A black dot on the device visible from the floor.
A device that is not part of a smoke management system would be:
a. A damper
b. A fan
c. A spot-type smoke detector
d. An ancillary device
What is a building element designed to limit the passage of heat, flame or smoke
a. Smoke control system
b. Stairwell pressurization system
c. Fire separation
d. All of the above
The National Fire Code requires that fire alarm systems be tested to what ULC standard?
a. CAN/ULC-S524
b. CAN/ULC-S527
c. CAN/ULC-S536
d. CAN/ULC-S572
The appropriate document that one needs to check to find out where automatic fire detectors are required
a. Fire Code
b. Building Code
c. CAN/ULC-S534
d. CAN/ULC-S537
Provincial authorities sometimes will pass amending legislation covering additions, alterations or deletions relative to the National Building Code?
a. True
b. False
The number of people allowed in a particular room, space or area of a building is referred to as the Occupant Load and is calculated with a formula consisting of:
a. The building height and its area divided by the assigned area per person
b. The assigned area per person and the building construction type, (combustible/non-combustible)
c. The assigned area per person and the building Occupancy type
d. The occupancy type and its height
The unit of measure for sound pressure level is the:
a. mA
b. PPM
c. dBA
d. CFM
The display section of a fire alarm panel provides
a. Alarm and trouble indications per zone
b. The closing of a sprinkler valve
c. A broken wire in a signal circuit
d. All of the above
This Federal Government organization publishes the National Building Code and the National Fire Code
a. Underwriters’ Laboratory of Canada
b. Canadian Fire Alarm Association
c. National Research Council
d. Canadian Council on Code Development
Part 6 of the National Fire Code covers the installation, inspection, testing, maintenance and operation of fire protection equipment. With respect to the testing of the fire alarm system specifically, the Code makes reference to:
a. The Electrical Code
b. ULC standard 524
c. The National Building Code, Part 3
d. ULC Standard S536
A smoke detector that can protect large open areas such as atriums and sanctuaries:
a. Is a beam detector
b. A duct detector
c. An Aspirating Detector
d. Doesn’t exist
The document mandating the procedure for performing a fire drill in a specific building is:
a. The building code
b. ULC Standard S537
c. The Fire safety Plan
d. The Fire Marshall’s Directive
A team of fire alarm technicians must bypass the fire alarm initiating circuits on three floor zones in a condominium. They will put a “fire watch” in place in accordance with
a. The Building Code
b. The building’s Fire Safety Plan
c. The building owner’s wishes
d. NFPA 72
An example of a Group A, Division 3 - type occupancy would be a:
a. Hospital with long term care
b. School with day care facility
c. Hazardous material manufacturing facility
d. Venue for basketball
The type of sprinkler system that is primarily used in areas where there is a possibility of freezing temperatures is a
a. Pre-action
b. Deluge
c. Gas suppression
d. Dry pipe
Annual tests and inspections of a fire alarm system must be performed by
a. The building owner or the owner’s agent
b. A person acceptable to the AHJ
c. A person familiar with the system operation
d. A sprinkler installer
A sprinkler system’s Alarm and Supervisory switches:
a. Are interchangeable
b. Are connected to and annunciated at, the fire alarm control panel and any remote annunciator
c. Have no connection to the fire alarm system.
d. Do not require testing.
When activated, typically creates a “curtain” of water.
a. A wet sprinkler system
b. A dry sprinkler system
c. A kitchen hood suppression system
d. A deluge system
The Building Code uses the term “Fire Detector” which refers to either :
a. A manual station or a waterflow switch
b. A smoke detector or a manual station
c. A heat detector or a smoke detector
d. A water flow switch or a heat detector
Sources of ignition include
a. Flame
b. Electric arcs
c. Radiation
d. All of the above
The audibility of a fire alarm audible signal in a bedroom of a Group C occupancy:
a. Will be a minimum of 75dBA, mandated by the Building Code
b. Will be a minimum of 65dBA, mandated by the Fire Code
c. Will be a minimum of 10 dBA above ambient, mandated by ULC standard S524
d. Must be loud enough to hear.
The evacuation “sound”, or tone, must be uniform throughout the building. Bells and horns cannot be used together?
a. True
b. False
Ancillary devices such as door-hold-open devices may be powered from the Control Unit if:
a. There is sufficient primary and secondary power available.
b. Specific connecting terminal points are provided in the panel.
c. The Control Unit is approved for this purpose
d. All of the above
Supervisory indicators are _____ in colour.
a. Yellow
b. Red
c. Blue
d. Green