Central Station Air Handlers Flashcards

1
Q

List the seven functions of a central station air handler as defined by ARI

A
Circulating
Cleaning
Heating
Cooling
Humidifying
Dehumidifying
Mixing Air
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

True or False? A packaged air handler offers a wider size range with more features and flexibility than a central station air handler?

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The size of a central station air handler is usually based on _____

A

the airflow through the unit and the cooling coil face area

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Name the two most common types of casing construction used in central station air handlers

A

post and panel, structural panel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Which of the following features is NOT generally found on an air handler designed for out-door installation? A.) Sloped roof with standing seams B.) Air inlet hood or louvers C.) High-quality gaskets and seals D.) Single wall, modular construction

A

D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

True or False? In a draw thru air handler, the cooling coil is located on the upstream or inlet side of the fan.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

True or False? Forward-curved fans are designed to operate at higher static pressures than airfoil fans.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Which of the following statements are true regarding AMCA fan class:____ A.) a class I fan may be operated under Class II or Class III performance requirements B.) a class II fan may be operated under Class III performance requirements C.) A Class III fan may be operated under Class II performance requirements. D.) All of the above

A

C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Under identical operation conditions A.) L50 200,000 hours = L10 40,000 hours B.) L50 500,000 = L10 40,000 C.) L50 represent the period of time all bearings of that type or designed will survive without fatigue failure D.) none of the above.

A

D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Which of the following air handler design features would more likely be found on a fully custom outdoor air handler than a standard central station AHU? A.) Sloped roof with standing seams B.) Outdoor intake hoods C.) Service and maintenance vestibules D.) G-90 galvanized casing panels

A

C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

True or False? A filter with a MERV 15 rating is likely to be a 2-inch deep flat panel filter

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

In a VAV system, which type of fan wheel could be operated without fan volume control (allowed to ride the fan curve)?_____ A.) Forward-curved B.) Backward-inclinedC.) Airfoil D.) Plenum

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Which types of energy recovery devices commonly provide both sensible and latent heat recovery? A.) Energy recovery wheels B.) Heat pipes C.) Run-around loops D.) fixed-plate heat exchangers

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

True or False? A dual-duct unit is a specific blow-thru configuration that can deliver cold and neutral or hot air simultaneously.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

True or False? In a multizone air handler, the fan and cooling coil are always selected based on the instantaneous block load of the area served by the air handler.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

The base placement of an ultraviolet light germicidal lamp (UV-c) within an air handler is immediately ____ A.) downstream of a cooling coil B.) upstream of a filter section C.) downstream of a heating coil D.) downstream of a mixing box

A

A

17
Q

Face and bypass dampers. A.) may be used as a means of capacity control for both heating and chilled water coils B.) minimize the possibility of coil freeze-up in cold climates C.) are not recommended with direct expansion cooling coils D.) all of the above.

A

D

18
Q

True or False? VFD has replaced IGV (inlet guide vanes) as the most common method of fan volume control.

A

True

19
Q

For a coil constructed of the same materials and face area, rank the following factors in order of their impact on cost, from highest to lowest: fin spacing, circuiting, rows.

A

rows, fin spacing, circuiting

20
Q

The primary reason for the recent market trend toward double-wall air handlers is:

A

double wall air handlers are perceived as higher quality