C Flashcards
Delta low voltage connection is connected in?
Parallel.
3 groups of 3 leads
9 leads at JB. T1-T9
3 leads are internal
What voltage is for low voltage and what voltage is for high voltage
Low = 230v
High - 460v
Wye low voltage is connected in?
Parallel
3 groups of 2 leads
1 group of 3 leads
Both delta and wye high voltage are connected in?
Series
Motor starters can be either?
Across the line starters or
Reduce full voltage starters
Full voltage starters typically produce a starting current that is?
500% - 600% of full load current and
Starting torque that is 150% of full load torque
Across the line starters can be?
Manual or magnetic starter design
Manual motor starters use a?
Manual open close switch
Magnetic starter uses?
Electrically operated switch
What are these symbols?
TDOE - time delay on energization
What are these symbols
TDOD
Timed delay on de energization
What kind of taps can an auto transformer have?
80, 65, or 50% taps
The starting currents % to the starter are?
64, 42 and 25% of full voltage starting current
Auto transformer starters can be?
Open or closed transition starters
Wye delta starting requires a Delta motor that has ____ terminal leads?
- T1- t6
Connected in wye for starting and reconnected in delta for running
When a motor is connected in wye to start, the in rush current and torque can be reduced to?
33 1/3%
For an open transition wye delta start the overload settings are based on?
57.7% of full load current
Which starter can be used as a disconnecting means by the CEC?
Manual