BS 9999 Flashcards
A system of smoke and heat ventilation should be provided from every basement storey that has:
a) a floor area of more than 200 m2; or b) a floor more than 3 m below the adjacent ground level
All manually openable vents provided for smoke control, whether in the stairs, in the lobby or into a shaft should
a) be outward opening;
b) not be top hung;
c) open a minimum of 30°;
d) be clearly identifiable and accessible;
e) be fitted with: 1) simple lever handles; or 2) rotary drives to simple rack or gear operated devices;
or 3) locks that can be readily and easily operated by the fire service.
Openings should be guarded to a height of not less than 1.1 m from floor level
Remotely openable vents
Openable vents situated above a stair should be provided with a remote control located adjacent to the fire service access doorway and clearly marked as to its function and means of operation
Automatic opening vents
Only the automatic vent from the lobby into the shaft on the floor where the smoke has been detected should open; all other lobby vents should remain closed.
Automatic opening vents opening to outside air should conform to BS EN 12101-2.
All connections between the smoke detection, vent control panels and actuator mechanisms should be within the fire-fighting shaft or control centre/room. Where any part of the control mechanism is powered by electricity, a secondary supply should be provided
A system of smoke and heat ventilation should be provided from every basement storey that has:
a) a floor area of more than 200 m2; or b) a floor more than 3 m below the adjacent ground level
If a basement is compartmented, each compartment should have direct access to venting without having to open doors, etc. into another compartment.
Smoke outlets should: a) be not less than 2.5% of the floor area of each storey;
b) be sited at high level, either in the ceiling or in the wall of the space they serve;
c) be as evenly distributed as possible around the perimeter of the building with no less than half the total vent area provided on two opposing walls, with the remaining half provided equally wherever possible, to discharge into the open air outside the building;
d) not be placed where they would prevent the use of escape routes from the building.
A system of powered smoke and heat ventilation may be provided as an alternative to natural venting, to remove smoke and heat from basements, ?
provided that the basement storey(s) are fitted with a sprinkler system. The sprinkler system should be in accordance with BS EN 12845 (new systems) or BS 5306-2 (existing systems
If a powered extract system is used, in a basement it should
provide ten air changes per hour;
b) be capable of handling gas temperatures of 300 °C for not less than 60 min;
c) come into operation automatically either on activation of the sprinkler system or by an automatic fire detection system conforming to BS 5839-1:2013 (at least L3 standard).
three methods of smoke clearance
horizontal cross-flow through the car park storey: natural cross-ventilation specified as permanent openings (Clause 7),
mechanical cross-ventilation achieved using conventional mechanical ventilation (Clause 8)
and mechanical cross-ventilation using jet fans (Clause 9).
Venting of smoke and heat from covered car parks
A system of smoke and heat ventilation, designed in accordance with BS 7346-7, with the objective of clearance of smoke during the fire and after the fire has been suppressed,
should be provided from every car park storey.
Smoke and heat ventilation from loading docks and covered service roadways
All enclosed loading docks exceeding 200 m2 and covered service roadways should be provided with a system of smoke
Smoke and heat ventilation from protected lobbies and protected corridors ( not firefighting )
the ventilation system should comprise either permanent ventilation of 0.4 m2 (minimum) geometric free area or be protected from the ingress of smoke by a mechanical smoke control system.
The mechanical smoke control system should be provided as follows. a) It should provide ten air changes per hour or a minimum of 2 m3/s, ensuring that a door opening force of 100 N is not exceeded.
b) It should be provided with a source of replacement air from outside.
c) It should, where appropriate, meet the recommendations in 27.1.3.
non FF lifts in the fire-fighting shaft may be fed from the same primary electricity supply, provided that:
he supply is adequate for this purpose; and b) arrangements are such that a fault occurring in any other lift in the fire-fighting shaft or power supplies will not affect in any way the operation of the firefighters lift.
The secondary supply should be of sufficient capacity to
maintain in operation:
• the firefighters lift and its ancillary equipment;
• normal lighting and other services within the fire-fighting shaft;
• the fire and rescue service communications system (see Clause 23);
• any powered ventilation or pressurization system which operates in conjunction with the operational use of the fire-fighting shaft;
• any pump(s) required to feed the fire main;
2) permit the automatic recall to fire and rescue service access level of all other lifts in the fire-fighting shaft, if necessary in sequence and at reduced speed.
An indication of the status of any of the following should be provided adjacent to the firefighters lift switch and duplicated in any fire control room:
i) the primary and secondary power supplies;
ii) any powered ventilation or pressurization systems; iii) any pumps feeding fire mains.
BS 9999 is designed as a coordinated package covering the four main areas that influence fire safety measures, namely:
• fire safety management; • the provisions of means of escape; • the structural protection of escape facilities and the structural stability of the building in the event of a fire; • the provision of access and facilities for fire-fighting